Publication 2707-UM005B-EN-P - July 2000
Installing the MicroView Operator Interface
6-3
Installation Instructions
1.
Cut an opening in the panel as shown on the next page.
Remove any sharp edges or burrs.
2.
Make sure the sealing gasket is properly positioned on the
terminal. This gasket forms a compression type seal. Do not
use sealing compounds.
3.
Install the four mounting nuts hand tight.
ATTENTION
!
Disconnect all electrical power from the panel
before making cutout.
Make sure that the area around the panel is clear.
Take precautions so that metal cuttings do not
enter any components that may be installed in
panel.
Failure to follow this warning may result in
personal injury or damage to the panel
components.
ATTENTION
!
Mounting nuts must be tightened to a torque of
10 inch pounds to provide a proper seal and to
prevent potential damage to the terminal.
Allen-Bradley assumes no responsibility for
water or chemical damage to the terminal or
other equipment within the enclosure because of
improper installation.
Summary of Contents for 2707-MVH232
Page 1: ...MicroView Operator Interface Module Catalog No 2707 MVH232 2707 MVP232 User Manual...
Page 6: ...Publication 2707 UM005B EN P Table of Contents iv...
Page 28: ...Publication 2707 UM005AB EN P 3 12 Initial Setup and Mode Menu...
Page 50: ...Publication 2707 UM005B EN P July 2000 6 6 Installing the MicroView Operator Interface...
Page 54: ...Publication 2707 UM005B EN P 7 4 Communication Connections and Setup...
Page 70: ...Publication 2707 UM005B EN P A 2 Specifications...
Page 74: ...Publication 2707 UM005B EN P B 4 MicroView Cable Diagrams...
Page 91: ...B...