Rockwell Automation Publication 20Y-TG001C-EN-P - April 2017
7
Preface
Summary of Changes
This manual contains new and updated information as indicated in the
following table.
Intended Audience
This manual is intended for qualified service personnel responsible for
troubleshooting and repairing the PowerFlex® Active Front End (AFE). You
must have previous experience with, and basic understanding of, electrical
terminology, procedures, required troubleshooting equipment, equipment
protection procedures and methods, and safety precautions. See safety-related
practices that are in Standard for Electrical Safety in the Work Place,
publication NFPA 70E.
What Is in This Manual
This manual contains hardware service information for the Frame 10
PowerFlex Active Front End. Verify that you are working on a Frame 10 by
checking the data nameplate on the AFE. The frame number is printed just
above the serial number.
What Is Not in This Manual
This manual does not contain installation, start-up, and programming
information. This information is available in the PowerFlex Active Front End
User Manual, publication
Topic
Page
Updated the basic one-line diagram for a Frame 10 AFE in IP20 2500 MCC style
enclosure to include the factory-installed common mode core at the DC bus output.
Updated the system schematics for a Frame 10 AFE in IP20 2500 MCC style enclosure to
include the factory-installed common mode core at the DC bus output.
Cat No.
20D
J
500 N 0 NNNBNNNN
UL Open Type/IP00
540V
650V
Normal Duty Power
250 kW
200 kW
450 kW
500 kW
Heavy Duty Power
DC Voltage Range
462 - 594
350
583 - 713
350
Amps
Input: DC,
AC Voltage Range
0 - 400
50 Hz
0 - 460
60 Hz
Base Hz (default)
Output: 3 Phase, 0 - 320Hz
Continuous Amps
420/500
630/550
420/500
630/550
1 Min Overload Amps
2 Sec Overload Amps
840/630
840/630
MFD. in 1989 on Nov 9
Frame #: 10
Serial Number: 2622381652
262238165
MADE IN THE USA (FAC 1B)
Series: A
Standard I/O: NONE
Original Firmware No. 2.04
U L
US
C
Æ
LISTED
IND CONT EQ
9D42
Cat No. 20D J 300 N 0 NNNBNNNN
UL Open Type/IP00
540V
650V
Normal Duty Power
160 kW
132 kW
250 kW
200 kW
Heavy Duty Power
DC Voltage Range
462 - 594
350
583 - 713
350
Amps
Input: DC,
AC Voltage Range
0 - 400
50 Hz
0 - 460
60 Hz
Base Hz (default)
Output: 3 Phase, 0 - 320Hz
Continuous Amps
300/245
330/368
300/245
330/368
1 Min Overload Amps
2 Sec Overload Amps
450/490
450/490
MFD. in 1989 on Nov 9
Serial Number: 2622381652
2622381652
MADE IN THE USA (FAC 1B)
Series: A
Standard I/O: NONE
Original Firmware No. 2.04
U L US
C
Æ
LISTED
IND CONT EQ
AFE
0/435
-842
Serial Number: 12345678
0035
Frame: 10
Data Nameplate on AFE in IP21
Rittal Enclosure
Data Nameplate on AFE in IP20
2500 MCC Style Enclosure