PowerFlex 750-Series Power Jumpers
Jumper Locations and Settings
The following pages show jumper locations and settings.
Jumper Locations and Settings
Frame
Vo
lt
ag
e
Cod
e Factory Default Jumper Settings
Power Source Type
Catalog Code ‘A’
Catalog Code ‘J’
1
B
C
D
PE-A jumper wire
connected to ground.
PE-B jumper wire
insulated/disconnected
from ground.
PE-A jumper wire and
PE-B jumper wire
connected to ground.
Solid Ground
Connect the MOV/Input Filter Cap jumper wire (PE-A) and
the CM Cap jumper wire (PE-B) to ground.
Non-Solid Ground
Insulate the MOV/Input Filter Cap jumper wire (PE-A) and
the CM Cap jumper wire (PE-B) from ground.
2
B
C
D
PE-A Installed
PE-B Not Installed
PE-A Installed
PE-B Installed
Solid Ground
Install jumper screws at ‘PE-A’ (MOV/Input Filter Cap) and
‘PE-B’ (CM Cap).
See
page 4
for recommended torque.
Non-Solid Ground
Remove both jumper screws.
3
B
C
D
E
PE-A Installed
PE-B Not Installed
PE-A Installed
PE-B Installed
Solid Ground
Install jumper screws at ‘PE-A’ (MOV/Input Filter Cap) and
‘PE-B’ (CM Cap).
See
page 4
for recommended torque.
Non-Solid Ground
Remove both jumper screws.
4
B
C
D
E
PE-A Installed
PE-B Not Installed
PE-A Installed
PE-B Installed
Solid Ground
Install Jumper screws at ‘PE-A’ (MOV/Input Filter Cap) and
‘PE-B’ (CM Cap).
See
page 4
for recommended torque.
Non-Solid Ground
Remove both jumper screws.
PE-A
PE-B
Insulated
Connected
Insulated
Connected
PE-B
PE-A
PE-B
PE-A
PE-B
PE-A