![Allen-Bradley 2080-DNET20 User Manual Download Page 83](http://html.mh-extra.com/html/allen-bradley/2080-dnet20/2080-dnet20_user-manual_2900147083.webp)
Rockwell Automation Publication 2080-UM004C-EN-E - March 2015
75
Specifications
Appendix
A
EFT/B immunity
IEC 61000-4-4:
±4 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on communication ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Environmental Specifications – 2080-DNET20
Attribute
Value