Rockwell Automation Publication 2080-UM004C-EN-E - March 2015
65
Specifications
Appendix
A
Step Response to 63%
(1)
5 ms
Current Load ln voltage output, max
10 mA
Resistive load on current output
0…500
Ω
(includes wire resistance)
Load range on voltage output
> 1k
Ω
@ 10V DC
Max. inductive load
(current outputs)
0.01 mH
Max. capacitive load
(voltage outputs)
0.1 µF
Overall Accuracy
(2)
Voltage Terminal: ±1% full scale @ 25 °C
Current Terminal: ±1% full scale @ 25 °C
Non-linearity (in percent full scale)
± 0.1%
Repeatability
(3)
(in percent full scale)
± 0.1%
Output error over full temperature range,
-20…65°C (-4…149°F)
Voltage: ± 1.5%
Current: ± 2.0%
Open and short-circuit protection
Yes
Output overvoltage protection
Yes
Input group to bus isolation
No isolation
Channel to channel isolation
Non-isolation
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...65 °C (-4…149 °F)
Temperature, non-operating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40...85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Operating altitude
2000 m
Cable length, max.
10 m
(1) Step response is the period of time between when the D/A converter was instructed to go from minimum to full
range until the device is at 63% of full range.
(2) Includes offset, gain, non-linearity and repeatability error terms.
(3) Repeatability is the ability of the output module to reproduce output readings when the same controller value is
applied to it consecutively, under the same conditions and in the same direction.
Output Specifications – 2080-OF2
Attribute
2080-OF2