FLEX I/O DC Input, Output, and Input/Output Analog Modules
7
Publication 1794-IN106D-EN-E - January 2014
Connect Wiring
Connect the wiring for the 1794-TB3G and 1794-TB3GS terminal bases as shown in the
following figure:
Terminal Base Wiring for the 1794-IE12/A Analog Input Module
ATTENTION:
To reduce susceptibility to noise, power analog modules and
digital modules from separate power supplies. Do not exceed a length of
10 m (33 ft) for DC power or analog I/O cabling.
ATTENTION:
Do not daisy-chain power or ground from this terminal base
unit to any AC or DC digital module terminal base units.
ATTENTION:
Do not exceed a length of 10 m (33 ft) for signal cabling.
I = Current
[1794-TB3G shown]
V=Voltage
C-0...C-11 = Returns for I or V connections 0...11
+24V DC = Terminals C-34 and C-50
COM = Terminals C-35 and C-51
Chassis ground (CG) = Terminals B-16, B-33, C-38, C-40...C-45, C-47
NC = No connection
For daisy-chaining: Supply in – C-34 (+) and C-35 (-)
Supply out – C-50 (+) and C-51 (-)
24V DC
Supply In
24V DC
Supply Out
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33