Linking Device Display Status
The display of the linking device provides status and diagnostic data in one of
three page formats: main page, H1 master page, or field device page. Use the
display Page button behind the front cover to scroll through the pages (see
for location of the Page button).
Main Page
The main page is the default display, and
the linking device returns to this page after
10 seconds.
H1Bus A/B:
Displays the bus voltages on
each port.
IP:
Displays the current IP address or
BOOTP if enabled.
STS:
Displays the status (see
Table 7
).
Table 7 - STS Status Descriptions
The lower portion of the main page shows the communication quality to each
field device as the percentage of data packets sent compared to data packets
received for each field device index (see
Table 8
).
Table 8 - Field Device Communication Quality
Status
Description
Ok
No events
New device found
New device on the bus
Redundancy ok
Masters are synchronized
Redundancy err
Masters out of sync
Bus A Tripped
Bus A over current trip
Bus B Tripped
Bus B over current trip
SAFE MODE
linking device set to Safe mode
Display
Communication Quality
Display
Communication Quality
>>>
95+
???
Unknown
>>
80+
OOS
Allocated, On-line, not Compelling Data
>
60+
Off
Allocated, Off-line
XXX
Below 60
Err
Allocated, On-line, not producing
Compelled Data
Summary of Contents for 1788-CN2FFR
Page 1: ...EtherNet IPandControlNettoFOUNDATIONFieldbusLinking Devices User Manual...
Page 6: ...4 Rockwell Automation Publication 1788 UM057B EN P September 2014 Table of Contents...
Page 17: ...Rockwell Automation Publication1788 UM057B EN P September 2014 15 Installation Chapter 1...
Page 92: ...90 Rockwell Automation Publication1788 UM057B EN P September 2014 Appendix D H1 Topology Notes...
Page 98: ...96 Rockwell Automation Publication1788 UM057B EN P September 2014 Glossary Notes...
Page 103: ......