Rockwell Automation Publication 1788-UM057B-EN-P - September 2014
47
Set Up in the Studio 5000 Logix Designer Application
Chapter 2
Reconnect Two Separate Running LAS Devices
If two masters are configured on a network (one on each end) and the cable
between them is broken, some devices will be connected to one master, and the
remaining devices will be connected to the other master.
See master modes 9, 12, and 15 in
Follow these steps to connect the two H1 segments.
1.
Hold the Page button for 5 seconds to put one of the masters into
Connect Safe mode
(see
You have 10 seconds to reconnect the segments.
2.
Reconnect the cable between the masters.
Swap Out Linking Devices
Follow these steps to swap out a linking device.
1.
Plug in all communication and power connectors, but not the H1
segment.
2.
Once the linking device is connected to Logix, change the node address to
anything other than the node address of the running master.
3.
Hold the Page button for 5 seconds to put the linking device into
Connect
Safe mode
(see
).
You have 10 seconds to reconnect the segments.
4.
Click the Master Sync button in the overview window to synchronize the
new master with the current running master (see
IMPORTANT
Failure to enter Connect Safe mode can result in a loss of
communication, or devices going to the visitor range.
IMPORTANT
Failure to enter Connect Safe mode can result in a loss of
communication, or devices going to the visitor range.
Summary of Contents for 1788-CN2FFR
Page 1: ...EtherNet IPandControlNettoFOUNDATIONFieldbusLinking Devices User Manual...
Page 6: ...4 Rockwell Automation Publication 1788 UM057B EN P September 2014 Table of Contents...
Page 17: ...Rockwell Automation Publication1788 UM057B EN P September 2014 15 Installation Chapter 1...
Page 92: ...90 Rockwell Automation Publication1788 UM057B EN P September 2014 Appendix D H1 Topology Notes...
Page 98: ...96 Rockwell Automation Publication1788 UM057B EN P September 2014 Glossary Notes...
Page 103: ......