Chapter 4
Issuing Scanner Management Commands
4-5
Table 4.B
Set Scan List Error Conditions
Error Mnemonic
Code
Description
SUCCESS
0
Scan list was valid.
SCANNER_NOT_PROGRAM
15
Scanner must be in Program mode.
SCAN_LIST_TOO_LONG
16
Scan list contains more than 64 entries.
SET_SCAN_LIST_IN_PROGRESS
17
A previous Set Scan List is already in progress.
AUTOCONFIGURING_IN_PROG
18
An Autoconfigure command is already in progress.
SCAN_LIST_CAUSES_FDG_ORPHAN
19
The new scan list would cause an orphan adapter address.
The address of the orphan is returned in the data byte of the confirmation.
A FDG orphan occurs when an adapter in the previous scan list was in a fault
dependent group but that adapter's address is not in the new scan list.
BAD_COMMAND_DATA_LENGTH
26
Command length is incorrect.
INVALID_ADAPTER_ADDRESS
49
Adapter address is greater than 127.
ADAPTER_SIZE_OVERLAP
51
Adapter sizes overlap each other.
ERROR_MORE_THAN_32_UNIQUE_DEVICES
53
A maximum of 32 unique adapters may be specified in a scan list.
instructs the scanner to replace the existing
scan list with the new one specified in the command. If the new scan list
would create a fault dependent group (FDG) orphan, the orphan’s address
is copied to the caller in addition to the status code.