Rockwell Automation Publication 1783-IN017A-EN-P - July 2017

5

ArmorStratix 5700 Ethernet Managed Switches

Mount the Switch

To mount the switch, follow these steps.

1. Position the rear panel of the switch against the wall or a panel in the desired location.

2. Place a number-10 screw that you provide through each mounting ear, and screw them into the wall.

Ground the Switch

Use at least 4 mm

(12 AWG) wire to connect to the external grounding screw. 

The ground lug is not supplied with the switch. You can use one of these options:

• Single ring terminal

• Two single ring terminals

To ground the switch to earth ground, follow these steps. Be sure to follow any grounding requirements at your site.

1. Use a Phillips screwdriver or a ratcheting torque screwdriver with a Phillips head to remove the ground screw from the front panel of the 

switch. 

Store the ground screw for later use.

2. Use the guidelines from the manufacturer to determine the wire length to be stripped.

3. Insert the ground wire into the ring terminal lug and use a crimping tool to crimp the terminal to the wire. 

If you are using two ring terminals, repeat this action for the second ring terminal.

4. Slide the ground screw through the terminal.

ATTENTION: 

To prevent bodily injury when mounting or servicing this unit in a rack, you must take special precautions to ensure that the system remains stable. 

The following guidelines are provided to ensure your safety: 

• This unit should be mounted at the bottom of the rack if it is the only unit in the rack. 
• When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack. 
• If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack. 

ATTENTION: 

To make sure that the equipment is reliably connected to earth ground, follow the grounding procedure instructions and use a suitable ring 

terminal lug, such as Thomas & Bett part number 10RCR or equivalent.

32477

32273-M

Summary of Contents for 1783-ZMS16TA

Page 1: ...GN 1783 ZMS8T8E2TGP 1783 ZMS8T8E2TGN Topic Page Parts List 4 RequiredTools 4 Site Requirements 4 Mount the Switch 5 Ground the Switch 5 Connect the Switch to a DC Power Source 6 Wire External Alarms 7...

Page 2: ...effettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento del...

Page 3: ...Chinese Markets ATTENTION ThisisaClassAInformationProduct Whenusedinaresidentialenvironment itmaycauseradiofrequencyinterference Undersuchcircumstances the user may be requested to take appropriate c...

Page 4: ...ch port regardless of the type of device on the other end of the connection SiteRequirements Observe these site requirements Clearance to front and rear panels meets these conditions Front panel statu...

Page 5: ...from the manufacturer to determine the wire length to be stripped 3 Insert the ground wire into the ring terminal lug and use a crimping tool to crimp the terminal to the wire If you are using two ri...

Page 6: ...nd M12 4 pin mini connector Rockwell Automation offers a Bulletin 1607 IP67 rated power supply to provide 24V DC power to the switch Ethernet communication and control power cables are available separ...

Page 7: ...tions for the Form C output alarm circuit are as follows NO output NC output common An alarm output and the common wiring connection are required to complete one output alarm circuit The Form C output...

Page 8: ...1 8 2 2N m 15 93 19 47 lb in for IP67 compliance Connectto10 100and100 1000Ports The switch 10 100 and 10 100 1000 ports automatically configure themselves to operate at the speed of attached devices...

Page 9: ...nto the RJ45 or M12 connector in the other device 10 100PoEPorts For PoE power supply requirements based on your application refer to page 7 1 Insert a straight through twisted four pair Category 5e o...

Page 10: ...er NEMAType 4 ATTENTION TheswitchisIP66 IP67 andNEMAType4 compliantonlywhenallIP66 IP67cablesarematedandtorquedappropriatelyorwiththesupplied dust caps attached Switch power input rating 12 48V DC 1 5...

Page 11: ...echnical Data publication 1783 TD001 Provides specification information for Ethernet switches and other devices Stratix Ethernet Switches User Manual publication 1783 UM007 Provides information about...

Page 12: ...eds better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pd...

Reviews: