background image

10

Rockwell Automation Publication 1783-IN017A-EN-P - July 2017

ArmorStratix 5700 Ethernet Managed Switches

Confirm Installation

To confirm the installation, power on the switch, and verify that the switch powers up. 

The time that is required for the switch to start up is directly related to your switch configuration. Start time is negatively affected by such things as 
the following:

• Spanning Tree Learning mode

• Number of files or images in onboard memory

To test the switch, follow these steps.

1. Power on the switch.

If the switch that is directly connected to a DC power source, locate the circuit breaker on the panel board that services the DC circuit, and 
move the circuit breaker to the On position.

2. Verify the start-up sequence.

The Setup status indicator blinks green as the IOS software image loads. If the routine fails, the Setup status indicator turns red.

Specifications

IMPORTANT

Start-up failures are usually fatal to the switch. Contact your Rockwell Automation representative immediately if your switch does not complete 
the start sequence successfully.

Attribute

1783-ZMS8TA

 1783-ZMS16TA

1783-ZMS24TA 

1783-ZMS4T4E2TGP, 
1783-ZMS4T4E2TGN

1783-ZMS8T8E2TGP, 
1783-ZMS8T8E2TGN

Temperature, operating

-40…+60 °C (-40…+140 °F

Temperature, ambient

60 °C (140 °F)

Enclosure type rating

IP66 rated for protection against dust and water jets
IP67 rated for protection against dust and submersion in water
NEMA Type 4

ATTENTION: 

The switch is IP66/IP67- and NEMA Type 4-compliant only when all IP66/IP67 cables are mated and torqued appropriately or with the supplied 

dust caps attached.

Switch power input rating

12…48V DC, 1.5 A

12…48V DC, 1.8 A

12…48V DC, 2.0 A

PoE/PoE +: 48…54V DC, 2.9 A
Non-PoE: 9.6…60V DC, 2.9 A

PoE/PoE+: 48…54V DC, 3.3 A
Non-PoE: 9.6…60V DC, 3.3 A

Alarm relay rating

30V DC, 1.0 A or 48V DC, 0.5 A

Isolation voltage

60 V (continuous), basic insulation type, DC power ports to ground, and PoE power ports to ground
No isolation between individual Ethernet ports
No isolation between PoE Power and Ethernet ports
No isolation between Console port and system

Wire size, ground connection

4.0 mm

2

 (12 AWG) min, stranded copper wire

Wire size, power connector for IP67 cable

 600V 16 AWG, 105 °C (221 °F)

Wire size, Alarm connector for IP67 cable

 300V, 22 AWG,105 °C (221 °F)

Torque, ground lug screw

0.4 N•m (3.5 in•lb)

Torque, power ports 

0.23 N•m (2.0 in•lb)

Torque, alarm, console, Ethernet ports 

(M12 connectors)

0.5…0.8 N•m (4.43…7.08 in•lb) for mating cables or dust caps

Torque, power supply connector 

(mini-change)

1.13 N•m (10 in•lb)

Torque, SD card door captive screws

1.8…2.2 N•m (15.93…19.47 in•lb)

Pilot duty rating

Alarm not rated

Operating and storage altitude

Up to 4570 m (15,000 ft)

Dimensions (H x W x D), approx

243.8 x 237.49 x 86.3 mm
9.6 x 9.35 x 3.4 in.

243.8 x 300.99 x 68.07 mm
9.6 x 11.85 x 2.68 in.

243.8 x 374.65 x 68.07 mm
9.6 x 14.75 x 2.68 in.

243.8 x 237.49 x 86.3 mm
9.6 x 9.35 x 3.4 in.

243.8 x 300.99 x 68.07 mm
9.6 x 11.85 x 2.68 in.

Weight

3.26 kg (7.19 lb)

3.30 kg (7.28 lb)

4.02 kg (8.86 lb)

3.26 kg (7.19 lb)

3.30 kg (7.28 lb)

Summary of Contents for 1783-ZMS16TA

Page 1: ...GN 1783 ZMS8T8E2TGP 1783 ZMS8T8E2TGN Topic Page Parts List 4 RequiredTools 4 Site Requirements 4 Mount the Switch 5 Ground the Switch 5 Connect the Switch to a DC Power Source 6 Wire External Alarms 7...

Page 2: ...effettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento del...

Page 3: ...Chinese Markets ATTENTION ThisisaClassAInformationProduct Whenusedinaresidentialenvironment itmaycauseradiofrequencyinterference Undersuchcircumstances the user may be requested to take appropriate c...

Page 4: ...ch port regardless of the type of device on the other end of the connection SiteRequirements Observe these site requirements Clearance to front and rear panels meets these conditions Front panel statu...

Page 5: ...from the manufacturer to determine the wire length to be stripped 3 Insert the ground wire into the ring terminal lug and use a crimping tool to crimp the terminal to the wire If you are using two ri...

Page 6: ...nd M12 4 pin mini connector Rockwell Automation offers a Bulletin 1607 IP67 rated power supply to provide 24V DC power to the switch Ethernet communication and control power cables are available separ...

Page 7: ...tions for the Form C output alarm circuit are as follows NO output NC output common An alarm output and the common wiring connection are required to complete one output alarm circuit The Form C output...

Page 8: ...1 8 2 2N m 15 93 19 47 lb in for IP67 compliance Connectto10 100and100 1000Ports The switch 10 100 and 10 100 1000 ports automatically configure themselves to operate at the speed of attached devices...

Page 9: ...nto the RJ45 or M12 connector in the other device 10 100PoEPorts For PoE power supply requirements based on your application refer to page 7 1 Insert a straight through twisted four pair Category 5e o...

Page 10: ...er NEMAType 4 ATTENTION TheswitchisIP66 IP67 andNEMAType4 compliantonlywhenallIP66 IP67cablesarematedandtorquedappropriatelyorwiththesupplied dust caps attached Switch power input rating 12 48V DC 1 5...

Page 11: ...echnical Data publication 1783 TD001 Provides specification information for Ethernet switches and other devices Stratix Ethernet Switches User Manual publication 1783 UM007 Provides information about...

Page 12: ...eds better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pd...

Reviews: