Rockwell Automation Publication 1783-IN017A-EN-P - July 2017

ArmorStratix 5700 Ethernet Managed Switches

Parts List

Verify that you have these items.

Required Tools

Obtain these tools:

• An IP67-rated cordset or patchcord with a female-end, 4-pin mini connector to provide 24V DC power to the switch

• Ratcheting torque screwdriver that exerts up to 1.69 N

m (15 in

lbs) of pressure

• #6 ring terminal lug for 5.3 mm

 (10 AWG) wire, such as Thomas & Bett part number 10RC6 or equivalent

• Crimping tool, such as Thomas & Bett part number WT2000, ERG-2001, or equivalent

• 5.3 mm

2

 (10 AWG) copper ground wire, such as Belden part number 9912 or equivalent

• Wire-stripping tool

• For panel-mounting without a DIN rail, M5 or #10-24 or #10-32 bolts or screws with 1.27 cm (0.5 in.) O.D. flat washers

For simplified cabling, the automatic medium-dependent interface crossover (auto-MDIX) feature is enabled by default on the switch. With 
auto-MDIX enabled, the switch detects the required cable type for copper Ethernet connections and configures the interfaces accordingly. You can 
use either a crossover or a straight-through cable for connections to a 10/100 or 10/100/1000 Ethernet switch port, regardless of the type of device 
on the other end of the connection.

Site Requirements

Observe these site requirements:

• Clearance to front and rear panels meets these conditions:

– Front-panel status indicators can be easily read.

– Access to ports is sufficient for unrestricted cabling.

– Front-panel DC power connectors and the alarm relay connector are within reach of the connection to the DC power source.

• To prevent the switch from overheating, observe the following minimum clearances:

– Top and bottom: 50.8 mm (2.0 in.)

– Sides: 50.8 mm (2.0 in.)

– Front: 50.8 mm (2.0 in.)

• Temperature surrounding the unit does not exceed 60 °C (140 °F).

• For 10/100 ports and 10/100/1000 ports, the cable length from a switch to an attached device cannot exceed 100 m (328 ft).

• For maximum noise immunity, X-code shielded cables must be used on M12 uplink ports. For recommended M12 media, refer to

http://ab.rockwellautomation.com/Connection-Devices/EtherNet-Media

.

• Cabling is away from sources of electrical noise, such as radios, power lines, and fluorescent lighting fixtures.

• Connect the unit to only an IP67-rated power supply. Rockwell Automation offers a Bulletin 1607 IP67-rated power supply to provide 

24V DC power to the switch.

1

ArmorStratix™ 5700 switch

2

Documentation

At the end of its life, this equipment should be collected separately from any unsorted municipal waste.

Summary of Contents for 1783-ZMS16TA

Page 1: ...GN 1783 ZMS8T8E2TGP 1783 ZMS8T8E2TGN Topic Page Parts List 4 RequiredTools 4 Site Requirements 4 Mount the Switch 5 Ground the Switch 5 Connect the Switch to a DC Power Source 6 Wire External Alarms 7...

Page 2: ...effettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento del...

Page 3: ...Chinese Markets ATTENTION ThisisaClassAInformationProduct Whenusedinaresidentialenvironment itmaycauseradiofrequencyinterference Undersuchcircumstances the user may be requested to take appropriate c...

Page 4: ...ch port regardless of the type of device on the other end of the connection SiteRequirements Observe these site requirements Clearance to front and rear panels meets these conditions Front panel statu...

Page 5: ...from the manufacturer to determine the wire length to be stripped 3 Insert the ground wire into the ring terminal lug and use a crimping tool to crimp the terminal to the wire If you are using two ri...

Page 6: ...nd M12 4 pin mini connector Rockwell Automation offers a Bulletin 1607 IP67 rated power supply to provide 24V DC power to the switch Ethernet communication and control power cables are available separ...

Page 7: ...tions for the Form C output alarm circuit are as follows NO output NC output common An alarm output and the common wiring connection are required to complete one output alarm circuit The Form C output...

Page 8: ...1 8 2 2N m 15 93 19 47 lb in for IP67 compliance Connectto10 100and100 1000Ports The switch 10 100 and 10 100 1000 ports automatically configure themselves to operate at the speed of attached devices...

Page 9: ...nto the RJ45 or M12 connector in the other device 10 100PoEPorts For PoE power supply requirements based on your application refer to page 7 1 Insert a straight through twisted four pair Category 5e o...

Page 10: ...er NEMAType 4 ATTENTION TheswitchisIP66 IP67 andNEMAType4 compliantonlywhenallIP66 IP67cablesarematedandtorquedappropriatelyorwiththesupplied dust caps attached Switch power input rating 12 48V DC 1 5...

Page 11: ...echnical Data publication 1783 TD001 Provides specification information for Ethernet switches and other devices Stratix Ethernet Switches User Manual publication 1783 UM007 Provides information about...

Page 12: ...eds better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature documents du ra du002_ en e pd...

Reviews: