Rockwell Automation Publication 1783-IN016B-EN-P - March 2019
9
Stratix 5700 Ethernet Managed Switches
Wire the DC Power Source
To wire the DC power source for the switch, follow these steps.
1.
Locate the power connector.
2.
Identify the positive and return DC power connections.
The positive DC power connection is labeled DC+, and the negative DC power connection is the adjacent connection labeled DC-.
3.
Measure a length of 0.82…0.52 mm
2
(18…20 AWG) copper wire long enough to connect to the DC power source.
4.
Use an 18-gauge wire-stripping tool to strip each of the two wires to 6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.).
Do not strip more than 6.8 mm (0.27 in.) of insulation from the wire. Stripping more than the recommended amount of wire can leave wire
exposed after installation.
5.
Loosen the two captive screws that attach the power connector to the switch, and remove the power connector.
Remove both connectors if you are connecting to two power sources.
6.
Insert the exposed part of the positive wire into the connection that is labeled DC+ and the exposed part of the return wire into the
connection labeled DC-.
Be sure that you cannot see any wire lead. Only wire with insulation can extend from the connector.
7.
Use a ratcheting-torque screwdriver to torque the captive screws of the power connector to 0.23 N•m (2.0 in•lb).
Do not exceed the recommended torque.
6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.)