Install the Alarm Relay Connector on the Switch

To attach the alarm relay connector to the front panel of the switch, follow these steps.

1.

Insert the alarm relay connector into the receptacle on the switch front panel.

2.

Use a ratcheting torque flathead screwdriver to tighten the captive screws on the sides of the alarm relay connector.

Wire the PoE Power Source

This procedure applies only to switches with PoE ports.The switch must be wired and grounded.

Power input requirements depend on your application.

1.

Measure a length of 0.82…0.52 mm

2

 (18…20 AWG) copper wire long enough to connect to the DC power source.

2.

Using an 18-gauge wire-stripping tool, strip each of the two wires to 6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.).

Do not strip more than 6.8 mm (0.27 in.) of insulation from the wire. Stripping more than the recommended amount of wire can leave wire 
exposed after installation.

3.

Locate the power connector.

4.

Insert the exposed part of the positive wire into the DC+ connection and the exposed part of the return wire into the DC- connection. 

Make sure that you cannot see any wire lead. Only wire with insulation can extend from the connector.

5.

Use a ratcheting-torque screwdriver to torque the captive screws of the power connector to 0.23 N•m (2.0 in•lb).

6.

Connect the other end of the positive wire (the one connected to DC+) to the positive terminal on the DC power source.

7.

Connect the other end of the return wire (the one connected to DC-) to the return terminal on the DC power source.

Application

Power Input per Port

Power Consumption

Allen-Bradley Products

PoE only 
IEEE 802.3af

44…57V DC (48V DC, nom)

15.4 W, max

Switched mode power supplies:
• 1606-XL Standard
• 1606-XLE Essential 
• 1606-XLP Compact 
• 1606-XLS Performance 

PoE and PoE + 
IEEE 802.3 at Type 2

50…57V DC (54V DC, nom)

15.4 W, max for PoE
30 W, max for PoE+

32290-M

6.3 mm (0.25 in.) ± 0.5 mm (0.02 in.)

DC+

DC-

Summary of Contents for 1783-BMS06SA

Page 1: ...6 Site Requirements 7 Mount the Switch 7 Ground the Switch 8 Wire the DC Power Source 9 Install the Power Connectors on the Switch 10 Wire External Alarms 11 Install the Alarm Relay Connector on the S...

Page 2: ...fettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell...

Page 3: ...inaresidentialenvironment itmaycauseradiofrequencyinterference Undersuchcircumstances the user may be requested to take appropriate countermeasures Prevent Electrostatic Discharge ATTENTION Thisequipm...

Page 4: ...as defined in EN 60664 1 when applied in Zone 2 environments The enclosure must be accessible only by the use of a tool This equipment shall be used within its specified ratings defined by Rockwell Au...

Page 5: ...ARNING RISQUE D EXPLOSION Couper le courant ou s assurer que l environnement est class non dangereux avant de d brancher l quipement Couper le courant ou s assurer que l environnement est class nondan...

Page 6: ...T2000 ERG 2001 or equivalent 5 3 mm2 10 AWG copper ground wire such as Belden part number 9912 or equivalent Wire stripping tool For panel mounting without a DIN rail M5 or 10 24 or 10 32 bolts or scr...

Page 7: ...theSwitch The switch ships with a spring loaded latch on the rear panel for mounting on a DIN rail To mount the switch on a DIN rail follow these steps 1 Position the rear panel of the switch directly...

Page 8: ...ratcheting torque screwdriver with a Phillips head Store the ground screw for later use 2 Use the guidelines from the manufacturer to determine the wire length to be stripped 3 Insert the ground wire...

Page 9: ...0 5 mm 0 02 in Do not strip more than 6 8 mm 0 27 in of insulation from the wire Stripping more than the recommended amount of wire can leave wire exposed after installation 5 Loosen the two captive s...

Page 10: ...and an optional secondary power source InstallthePowerConnectorsontheSwitch To install the switch power connectors to the front panel of the switch follow these steps 1 Insert one power connector into...

Page 11: ...ction are required to complete one input alarm circuit You must provide either an NO or an NC dry contact to complete the alarm circuit between reference ground and IN1 or IN2 The three remaining conn...

Page 12: ...or the external alarm device into the connections that are based on an alarm input or output circuit setup See Table on page 11 5 Use a ratcheting torque flathead screwdriver to torque the captive scr...

Page 13: ...wire Stripping more than the recommended amount of wire can leave wire exposed after installation 3 Locate the power connector 4 Insert the exposed part of the positive wire into the DC connection an...

Page 14: ...s Once you install SFP modules in the switch be aware that the overall temperature rating of the combined modules switch and SFP modules is limited to the lowest maximum temperature rating and the hig...

Page 15: ...e it from the module slot f Place the removed SFP module in an antistatic bag or other protective environment InstallorRemovetheSDCard To install or replace the optional SD card follow these steps 1 O...

Page 16: ...Connectto10BASE T 100BASE TX or1000BASE TPorts To connect to 10BASE T 100BASE TX or 1000BASE T ports follow these steps 1 Choose one of these options to connect a device When connecting to workstatio...

Page 17: ...le port and fiber optic cable and store them for future use 2 Insert one end of the fiber optic cable into the SFP module port 3 Insert the other cable end into a fiber optic receptacle on a target de...

Page 18: ...ected by such things as the following Spanning Tree Learning mode Number of files or images in onboard memory To test the switch follow these steps 1 Apply power to the switch If the switch is directl...

Page 19: ...rm relay 30V DC 1 0 A or 48V DC 0 5 A Isolation voltage 60V continuous basic insulation type DC power ports to ground and PoE power ports to ground No isolation between individual Ethernet ports No is...

Page 20: ...rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center Knowledgebase Articles How toVideos FAQs Chat User Forums and Product Notification Updates https r...

Reviews: