Allen-Bradley 1783-BMS06SA Installation Instructions Manual Download Page 11

Rockwell Automation Publication 1783-IN016B-EN-P - March 2019

11

Stratix 5700 Ethernet Managed Switches

Wire External Alarms

The switch has two alarm inputs and one Form C (single-pole, double-throw) alarm output relay circuits for external alarms. The input alarm relay 
circuits are designed to sense if the alarm input is open or closed relative to the alarm input reference pin. The output alarm relay circuit has one 
Form C relay, with one normally open (NO) and one normally closed (NC) contact. You can configure the output alarm relay as either normally 
energized or normally de-energized by using the CLI.

Alarm signals are connected to the switch through the 6-way alarm relay connector. Three connections are dedicated to the two alarm input circuits:

• Alarm input 1 (IN1)

• Alarm input 2 (IN2)

• Isolated reference ground

An alarm input and the reference ground wiring connection are required to complete one input alarm circuit. You must provide either an NO or an 
NC dry contact to complete the alarm circuit between reference ground and IN1 or IN2.

The three remaining connections for the Form C output alarm circuit are as follows:

• NO output

• NC output

• common

An alarm output and the common wiring connection are required to complete one output alarm circuit. The Form C output alarm relay provides 
one NO and one NC dry contact.

The labels for the alarm relay connector are on the switch panel.

ATTENTION: 

Do not apply an external voltage source to either the IN1 or IN2 alarm inputs. Limit alarm output wiring to 48V DC, 0.5 A.

ATTENTION: 

Wire connections to the power and relay connector, must be UL- and CSA-rated, style 1007 or 1569 twisted-pair copper appliance wiring 

material (AWM) wire.

Alarm Relay Connector Labels

Label

Connection

NO

Alarm Output Normally Open (NO) connection

COM

Alarm Output Common connection

NC

Alarm Output Normally Closed (NC) connection

IN2

Alarm Input 2

REF

Alarm Input Reference Ground connection

IN1

Alarm Input 1

Summary of Contents for 1783-BMS06SA

Page 1: ...6 Site Requirements 7 Mount the Switch 7 Ground the Switch 8 Wire the DC Power Source 9 Install the Power Connectors on the Switch 10 Wire External Alarms 11 Install the Alarm Relay Connector on the S...

Page 2: ...fettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell...

Page 3: ...inaresidentialenvironment itmaycauseradiofrequencyinterference Undersuchcircumstances the user may be requested to take appropriate countermeasures Prevent Electrostatic Discharge ATTENTION Thisequipm...

Page 4: ...as defined in EN 60664 1 when applied in Zone 2 environments The enclosure must be accessible only by the use of a tool This equipment shall be used within its specified ratings defined by Rockwell Au...

Page 5: ...ARNING RISQUE D EXPLOSION Couper le courant ou s assurer que l environnement est class non dangereux avant de d brancher l quipement Couper le courant ou s assurer que l environnement est class nondan...

Page 6: ...T2000 ERG 2001 or equivalent 5 3 mm2 10 AWG copper ground wire such as Belden part number 9912 or equivalent Wire stripping tool For panel mounting without a DIN rail M5 or 10 24 or 10 32 bolts or scr...

Page 7: ...theSwitch The switch ships with a spring loaded latch on the rear panel for mounting on a DIN rail To mount the switch on a DIN rail follow these steps 1 Position the rear panel of the switch directly...

Page 8: ...ratcheting torque screwdriver with a Phillips head Store the ground screw for later use 2 Use the guidelines from the manufacturer to determine the wire length to be stripped 3 Insert the ground wire...

Page 9: ...0 5 mm 0 02 in Do not strip more than 6 8 mm 0 27 in of insulation from the wire Stripping more than the recommended amount of wire can leave wire exposed after installation 5 Loosen the two captive s...

Page 10: ...and an optional secondary power source InstallthePowerConnectorsontheSwitch To install the switch power connectors to the front panel of the switch follow these steps 1 Insert one power connector into...

Page 11: ...ction are required to complete one input alarm circuit You must provide either an NO or an NC dry contact to complete the alarm circuit between reference ground and IN1 or IN2 The three remaining conn...

Page 12: ...or the external alarm device into the connections that are based on an alarm input or output circuit setup See Table on page 11 5 Use a ratcheting torque flathead screwdriver to torque the captive scr...

Page 13: ...wire Stripping more than the recommended amount of wire can leave wire exposed after installation 3 Locate the power connector 4 Insert the exposed part of the positive wire into the DC connection an...

Page 14: ...s Once you install SFP modules in the switch be aware that the overall temperature rating of the combined modules switch and SFP modules is limited to the lowest maximum temperature rating and the hig...

Page 15: ...e it from the module slot f Place the removed SFP module in an antistatic bag or other protective environment InstallorRemovetheSDCard To install or replace the optional SD card follow these steps 1 O...

Page 16: ...Connectto10BASE T 100BASE TX or1000BASE TPorts To connect to 10BASE T 100BASE TX or 1000BASE T ports follow these steps 1 Choose one of these options to connect a device When connecting to workstatio...

Page 17: ...le port and fiber optic cable and store them for future use 2 Insert one end of the fiber optic cable into the SFP module port 3 Insert the other cable end into a fiber optic receptacle on a target de...

Page 18: ...ected by such things as the following Spanning Tree Learning mode Number of files or images in onboard memory To test the switch follow these steps 1 Apply power to the switch If the switch is directl...

Page 19: ...rm relay 30V DC 1 0 A or 48V DC 0 5 A Isolation voltage 60V continuous basic insulation type DC power ports to ground and PoE power ports to ground No isolation between individual Ethernet ports No is...

Page 20: ...rockwellautomation com idc groups literature documents du ra du002_ en e pdf Technical Support Center Knowledgebase Articles How toVideos FAQs Chat User Forums and Product Notification Updates https r...

Reviews: