30
Rockwell Automation Publication IASIMP-QS023B-EN-P - December 2012
Chapter 1
Prepare the CompactLogix 5370 L3 Controller Hardware
4.
Connect the 1769-SDN module’s
grounding screw to the panel.
Use 2.08 mm
2
(14 AWG) wire to
connect to panel ground.
5.
Connect the QD Micro Cordset
to a KwikLink sealed
microconnector on the network.
6.
Wire the 1606-XLDNET8 DeviceNet power supply.
a. Connect incoming power to the power supply.
b. Place the switch in the position that matches your supply voltage.
WARNING:
Verify that all incoming power is turned off before wiring power.
Connect
To
V AC COM
N (neutral)
120/240V AC
L (line)
Ground
Grounding Screw