Produce and Consume a Tag
Chapter 1
Rockwell Automation Publication 1756-PM011J-EN-P - February 2018
29
2.
Click the
Advanced
tab.
3.
Select the
Allow Consumed Tags to Use RPI Provided by Producer
check box to allow for the RPI negotiation.
Important:
The check box is only available when the controller is offline. If the
check box is not checked, the consuming controller does not
accept the RPI provided by the producer if the consuming
controller requests an RPI that is out of the producer’s configured
RPI range. As a result, an out-of-range RPI request results in a
failed connection.
4.
Click
OK
.
When a consuming controller accepts a default RPI by a producing
controller, you can verify the acceptance and the RPI value on the
Consumed Tag Connection
dialog box.
Before you begin:
•
The controller must be online and the consumed tag is connected with
the producer providing the RPI.
To verify consumed tag acceptance and RPI value:
1.
In the
Controller Organizer
, right-click the
Controller Tags
folder
and click
Edit Tags
.
Verify consumed
tag acceptance