Produce and Consume a Tag
Chapter 1
Rockwell Automation Publication 1756-PM011J-EN-P - February 2018
33
The RPI is outside the range of the producing controller’s RPI Limits.
There is no default RPI that is set up for the producing controller.
Version 17 and earlier:
The RPI requested by the consumed tag is not
within the range of the producer. The connection is rejected and a 0111 error
is reported that the connection failed. You must re-enter an RPI that is within
the range configured on the produced tag. If a version 17 consumer is trying
to connect with a version 18 producer and the RPI is outside the range of the
producer and there is no default set up, a 0111 error reports the connection
failed.
Tip:
See
on
for an explanation of the error messages.
Version 18 and later:
The RPI requested by the consumed tag is not within
the RPI limitation range of the producer. The producer is not set up to
provide a default RPI, so a 0111 error message is reported that the
connection failed. You must re-enter an RPI that is within the range
configured for the producer because there is no RPI default negotiation with
the consumer.
Scenario 2