Troubleshoot the Linking Device
Appendix A
2.
Press the reset button.
Reset through RSFieldbus Software
By using RSFieldbus software, you can reset the linking device through the
Restart parameter in the Resource block.
1.
While online in RSFieldbus software, right-click the Resource block of the
linking device and choose Online Characterization.
2.
Select the Restart parameter and click Edit.
3.
On the pull-down menu, choose the type of reset identified in the table.
ATTENTION:
You will lose the following linking device functions during
a reset:
•
Control of the current linking device process
•
Monitoring processes through the linking device
•
Communication to devices attached to the linking device
Value
Reset Type
Description
1
Run
Run appears while the linking device is operating
normally. It returns to this value after a reset value
(default or factory) is transmitted
and completed.
2
Resource
Not supported (do not select).
3
Defaults
This resets all block parameters to default. All
blocks in the linking device are retained, including
tag names, and macrocycle times.
4
Processor
Not supported (do not select).
5
Factory
This deletes all blocks in the linking device except
for the Resource block. All Resource block
parameters are reset to factory default, including
the tag name.
43481-C
Reset Configuration Jumper
Factory-default Reset Button
(inside top cover)
Summary of Contents for 1757-FFLD2
Page 8: ...8 Rockwell Automation Publication 1757 UM012A EN P July 2011 Table of Contents Notes...
Page 10: ...10 Rockwell Automation Publication 1757 UM012A EN P July 2011 Preface Notes...
Page 178: ...178 Rockwell Automation Publication 1757 UM012A EN P July 2011 Glossary Notes...
Page 182: ...182 Rockwell Automation Publication 1757 UM012A EN P July 2011 Index Notes...
Page 183: ......