Safety Integrity Level (SIL) Concept
SIL 3 Certification
1756 and 1768 GuardLogix® controller systems are
type-approved
and certified
for use in safety applications up to and including SIL CL3 according to
IEC 61508 and IEC 62061, safety applications up to and including Performance
Level PLe (Category 4) according to ISO 13849-1. SIL requirements are based
on the standards current at the time of certification.
In addition, the standard tasks within 1756 GuardLogix controllers can be used
either for standard applications or SIL 2 safety applications as described in the
Using ControlLogix® in SIL 2 Applications Reference Manual, publication
. In either case, do not use SIL 2 or standard tasks and variables to
build up safety loops of a higher level. The safety task is the only task certified for
SIL 3 applications.
The standard task in 1768 Compact GuardLogix controllers may not be used for
SIL 2 safety applications.
RSLogix 5000® programming software is required to create programs for 1756
and 1768 GuardLogix controllers.
Topic
Page
GuardLogix Architecture for SIL 3 Applications
GuardLogix PFD and PFH Specifications
Safety Integrity Level (SIL) Compliance Distribution and Weight
Safety Task Period and Safety Task Watchdog