Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
196
Configure POINT I/O Modules in RSLogix 5000 Software
2.
Check the Calibrate checkbox to specify which channel to calibrate.
3.
Under Calibrate Channels, select One At a Time.
4.
Click Start Calibration, which is active when the system is online, and you
selected at least one of the channels.
Note that when you press the F1 button on your keyboard or click Help
from the wizards and warning messages that appear during calibration, you
get detailed information about related procedures.
You see a Danger dialog.
5.
From the Danger dialog, for a module not currently used for control, click
OK.
You see the Low Value dialog.
6.
From the Low Value dialog, click Next to start calibration.
You see the High Value dialog.
7.
From the High Value dialog, click Next to start calibration.