Calibrate Your Analog Modules
125
Calibrate the Analog
Current Output Module
To calibrate your output module, connect the module in a DeviceNet system
similar to that shown in the figure, and use this procedure.
1.
Double-click the icon to bring up the General parameter dialog.
You see the EDS editor ask you if you want to upload the configuration
from the device.
IMPORTANT
Apply power to the power supply and module for at least
10 minutes before calibrating the module. This allows
internal temperatures to stabilize and reduces drift errors.
0
1
0
1
0
1
0
1
0
1
0
1
44032
Power Supply Voltage
DeviceNet Input
PDN OE2C
250
Ω
Current Meter
Channel 0
Connect to 0 and 4
Channel 1
Connect to 1 and 5