Rockwell Automation Publication 1734-UM001E-EN-P - July 2013
Troubleshoot with the Indicators
153
Indication
Probable Cause
Recommended Action
POINTBus Status
Off
Device not powered - check module status indicator.
Apply power to device.
Alternating red/green
LED power cycle test is present.
None.
Flashing red
Recoverable fault has occurred:
•
At power up the number of expected modules does not equal the number of
modules present
•
A module is missing
•
Node fault (I/O connection timeout)
•
Change chassis size to match number of
modules present.
•
Replace missing module.
•
Check for I/O Module failure and correct, as
needed.
Flashing green
Adapter online with no connections established.
•
Adapter chassis size has not been configured
•
Controller in program/idle mode
•
ControlNet cable break
•
Firmware (NVS) update
•
Set adapter chassis size.
•
None.
•
Check cable and connect, as needed.
•
Complete firmware update.
Solid green
Adapter online with connections established (normal operation, in run mode) None.
Solid red
Unrecoverable fault occurred - the adapter is bus off.
1. Cycle power to device.
2. If condition persists, replace device.
Indication
Probable Cause
Recommended Action
ControlNet A/B Status
Viewed Together (A and B)
Both Steady Off
Reset, no power, or entire network interface deactivated.
None or cycle power.
Alternating red/green Self test mode is present.
None.
Alternating red/Off
Incorrect configuration is present.
Check network address and other ControlNet
configuration parameters.
Both Steady red
Faulted unit is present.
Cycle power or reset unit. If fault persists, contact
A-B representative or distributor.
Viewed Individually (A or B)
Steady Off
Channel disabled.
Program network for redundant media, if required.
Flashing red/green
Incorrect network configuration is present.
Cycle power or reset unit. If fault persists, contact
A-B representative or distributor.
Flashing red/Off
•
Media fault.
•
No other nodes present on network.
•
Check media for items such as broken cables,
loose connectors, and missing terminators.
•
Add other nodes to the network.
Flashing green/Off
•
Temporary channel errors are present.
•
Node is not configured to go on line.
Make sure the configuration manager node is
present and working and selected address is not
greater than selected UMAX.
(1)
Steady green
Normal operation - MAC frames are being received without detected errors.
None.
(1) The configuration manager node is the node responsible for distributing ControlNet configuration data to all nodes on the network.
Summary of Contents for 1734-OB2
Page 4: ...Publication 1734 UM001E EN P July 2013 iv Summary of Changes Notes...
Page 16: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 xxiv Notes...
Page 22: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 6 About the Modules Notes...
Page 116: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 118 POINT I O Module Data Notes...
Page 168: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 176 Default Data Maps Notes...
Page 172: ...Rockwell Automation Publication 1734 UM001E EN P July 2013 180 Mounting Dimensions Notes...