42
Rockwell Automation Publication 1718-UM001A-EN-E - December 2019
Appendix C
Additional HART Protocol Information
62
Read analog
outputs
0
1
2
3
(2)
Analog output number;
code for slot 0
Analog output number;
code for slot 1
Analog output number;
code for slot 2
Analog output number;
code for slot 3
(4)
0
1
2…5
6
7
8…11
12
13
14…17
18
19
20…23
Slot 0 analog output number code
Slot 0
Slot 0 level
Slot 1
Slot 1
Slot 1 level
Slot 2
Slot 2
Slot 2 level
Slot 3
Slot 3
Slot 3 level
(8)
(F)
(F)
(F)
(F)
63
Read analog
output
information
0
Analog output number
code
0
1
2
3
4…7
8…11
12…15
Analog output number code
Analog output alarm select code
Analog output transfer function code
Analog output range units code
Analog output upper-range value
Analog output lower-range value
Analog output additional damping value
(seconds)
(F)
(F)
(F)
64
Write analog
output additional
damping value
0
1…4
Analog output number
code
Analog output
additional damping
value (seconds)
(F)
As in command
65
Write analog
output range
value
0
1
2…5
6…9
Analog output number
code
Analog output range
units code
Analog output upper-
range value
Analog output lower-
range value
(F)
(F)
66
Enter/exit Fixed
Analog Output
mode
0
1
2…6
Analog output number
code
Analog output units
code
Analog output level
(5)
(F)
67
Trim analog
output zero
0
1
2…6
Analog output number
code
Analog output units
code
Externally measured
analog output level
(F)
68
Trim analog
output gain
0
1
2…6
Analog output number
code
Analog output units
code
Externally measured
analog output level
(F)
69
Write analog
output transfer
function
0
1
Analog output number
code
Analog output transfer
function code
70
Read analog
output endpoint
values
0
Analog output number
code
0
1
2…5
6…9
Analog output number code
Analog output endpoint units code
Analog output upper endpoint value
Analog output lower endpoint value
Table 4 - Common Practice Commands
Command
Data in Command
Data in Reply
Contained in
No.
Function
Byte
Data
Type
(6)
Byte
Data
Type
(6)
Input
Tag
CIP MSG