4 Maintenance, cleaning, and disinfection
© 2022 Interflex Datensysteme GmbH | IF-261 Cabinet Lock | 06.22
27
If you ignore the battery warnings, there is a chance that the Cabinet Lock may fail. In such
case, the battery compartment is no longer accessible. To replace the batteries, you can
connect it to an emergency power supply.
Emergency power supply
The Cabinet Lock possesses a micro USB port for emergency
power supply using standard power banks.
4.2 Reset (cold boot)
In the event of an error or a system change, you can reset the component to its factory settings
(reset, cold boot). In the process, all internal data such as booking memory, time profiles and door
groups are deleted.
Cold boot with DoorManager software
Prerequisites
ü
You have logged in using the
Facility card
or
Site/Installation
mode.
Procedure
u
Click the
cold start
button
The LED lights up in purple for 12 seconds, then orange for 10 seconds, and finally red for 2
seconds.
Initiate a reset manually on the component
1. Dismount the component so that the reset button is accessible
2. Remove the battery case
3. Replace the battery case
The LED lights up in orange for 10 seconds (no flashing).
4. Press the reset button while the LED is lit
5. Press the reset button for more than 3 seconds
Reset is carried out.
Battery status is checked.
6. Opendor
air
only: Press the reset button for more than 10 seconds
Component and IF-4041 Gateway are unpaired
At the end of the procedure, the LED lights up in purple for several seconds.