Alke AP-1 Series User, Service And Installation Manual Download Page 8

 

Version: April 2018

 

manual number: 0009 0420EN

 

Service and maintenance 

General 

The  frequency  of  maintenance  is  strongly  depending  on  the  quality  of  the  combustion  air  and  the 
intensity of use. When used in poultry houses, maintenance is advised every 6 weeks or by changing 
the animals. By use in clean environment conditions, the maintenance period can be extended but not 
longer than 6 months. In case heaters are not used for a long period, always do maintenance first before 
using them again. Wear safety goggles during cleaning with compressed air. 
 
Parts that are broken, or are not functioning well, must be replaced directly by identical ones of same 
brand and type. Consult the dealer or manufacturer in case of doubt. 
 
WARNING:  always  switch  off  the  heater  and  isolate  the  gas  before  carrying  out  any  service  or 
maintenance operation. 
 

Order of maintenance 

 

First clean the heater and filter as described below by daily maintenance. Take the venturi out during 
cleaning to remove dust directly behind it. 

 

Clean the reflector and other parts (excluding the burner tube  and  venturi  gauze) with  water and 
mild detergent and a cloth or soft brush. 

 

Carefully inspect the burner tube and venturi gauze on damage, cracks and holes. Replace when 
needed. 

 

Check the injector for obstructions. Remove obstructions by brushing them away and by using a pin 
or drill to clean the injector hole. Make sure that the injector hole does not become wider by using a 
pin or drill that is larger than the size stamped on the side of the injector.  

 

Clean  the  inside  of  the  gas  safety  device  and  injector  with  compressed  air.  Make  sure  that  the 
pressure of the compressed air is not larger than the 1,5x the pressure stamped on the safety device 
(65 or 1400 mbar). Otherwise the rubber seals inside the safety device will become damaged. 

 

Check the condition of the thermocouple sensor. Replace in case the tip is burnt-in already to avoid 
unnecessary shut down later on.  

 

Check all gas carrying parts and connections for gas tightness with leak detection liquid or soapy 
water according the procedure in the standards applicable in the local installation situation. Never 
use a flame for soundness checks! 

 

In  case  a  gas  hose  is  used,  check  this  carefully  for  cracks,  wear  and  other  signs  of  damage  or 
alteration. Replace it also when the maximum lifetime printed on the hose, or the maximum allowed 
by local requirements, has passed.  

 

Commission  the  heater  after  maintenance  and  check  it  carefully  during  first  ignition,  firing  and 
extinguishing. 

In case the heaters need to be stored for a long time, make sure that no dust, spiders, etc. can enter 
the heater. Use the carton packaging box to store the heater, or a plastic bag if the box is not available 
anymore, and close this carefully.  
 

Daily maintenance  

In  dusty  or  dirty  environments  check  and  clean  a  heater  every  day.  In  case  a  heater  is  not  cleaned 
internally the heat efficiency will drop and the lifetime of the burner tube and venturi gauze will become 
shorter or they will be destroyed. Also, there is a possibility that carbon monoxide (poisonous) will be 
produced  and  soot  deposit  will  occur.  To  keep  the  heater  internally  and  externally  free  of  dust  is 
important. Inspect and clean also every day the combustion air openings into the building and the proper 
functioning of exhaust fans. 
 

Dust filter 

Dust filters must be check every day and cleaned in case needed. Remove a filter before cleaning. Dry 
dust can be removed by tapping the filter softly against a solid surface like the sole of a shoe. The dust 
will fall off easy now. In case the filter is still not clean, brush the surface gently with a brush or clean it 
with compressed air from inside to the outside. In case the dust is greasy, clean the filter in warm water 
with a bit detergent. Make sure that filters are dry before placing them back. Even with the use of a filter 
still check the heater regularly inside while very fine dust still will pass the filter and pollute the heater 
internally. 
 
Advice: Lots of farmers use a second set of dust filters. They replace the dusty ones directly with the 
clean ones and clean the filters outside the barn to avoid unneeded disturbance of the animals.  

Summary of Contents for AP-1 Series

Page 1: ...infra red heaters for use in well ventilated areas Country of destination GB IE MT General international manual AP 1 AP 3 AP 2 AP 1 F AP 3 F AP 3 FT AP 2 F AP 2 FT Alke BV Industrielaan 11a 3925 BD S...

Page 2: ...t so that nobody accidentally operates the heater Store the heater in a safe place mark that it cannot be used and contact a service agent or gas installer to solve the problem This heater has an open...

Page 3: ...nature of gas and pressure and adjustment of the appliance are compatible Make sure that the gas and gas line are clean Install a gas filter and condensate trap before the heaters in case the gas or...

Page 4: ...for more details Beside other important requirements this standard states in short that a 1 5 times room air replacement per hour is sufficient in most situations Also a maximum of 5W heat input per...

Page 5: ...the gas supply to the burners to extinguish the flames In addition it makes it possible to remove the heaters after use or to service the heaters safely The gas inlet at the heater side is standard a...

Page 6: ...and away from other people Check if there are no other operating heaters other gas heaters burning candles or people smoking cigarettes in the area Be sure that the valve on the gas cylinder is close...

Page 7: ...ly one pressure is mentioned adjustment is not possible and only continuous operation or on off operation is allowed AP 1 2 3 FT version Make sure that the gas supply pressure remains constant at the...

Page 8: ...r gas tightness with leak detection liquid or soapy water according the procedure in the standards applicable in the local installation situation Never use a flame for soundness checks In case a gas h...

Page 9: ...he gas safety device are the most important parts that maybe requires replacement during normal operational life See the Parts List for more information Replacement thermocouple and magnet unit positi...

Page 10: ...ing Wrong gas or pressure is used Check data plate with the gas supply Check if the injector or venturi are blocked or dirty Check the injector and venturi size with the table Check if pipe sizes or g...

Page 11: ...2510000 Burner AP 3 50x80 mm 7 07009000 Distance ring 26 03856000 Suspension frame 155mm AP 2 8 01301000 Injector holder 27 013070xx Venturi 25x62 consult factory 9 01161xxx Injector M8x0 75 consult f...

Page 12: ...x x I3P G31 1400 20 5 6 0 65 T 1 2 400 g h 0 47 0 22 10 5 1 0063CS3936 I3P G31 1400 20 4 6 0 55 329 g h 0 45 x 11 4 x Ha 1400m I3P G31 2000 20 5 4 0 5 T 1 4 386 g h 0 41 0 22 10 4 x x AP 3 series I2L...