background image

Installation 

 

 

 

 

3-6

 

Algas-SDI Operations and Maintenance Manual – P/N – 54702

 

AIR SUPPLY 

1.  Air filters may be required on the air supply and instrument air.  The user must 

determine the cleaning schedule for the filters.  Dirty air will cause problems in 
the mixing systems.  Oil carryover must be less than 2 PPM.  Particulates greater 
than one micron must be removed.  Temperature must be less than 130F.  
Dewpoint must be 2 deg. F below the temperature of air entering the mixer. 

2.  An air dryer for the incoming air supply will be required if water vapor could 

condense in the air supply lines. 

3.  A properly sized first-stage air pressure regulator is required to be installed 

upstream of the mixer compressed air inlet.   The air supply pipe to this regulator 
must not be more than 150 psi. 

VAPOR SUPPLY 

1.  A properly sized first-stage gas supply pressure regulator is required to be 

installed upstream of the mixer LPG vapor inlet.  This regulator reduces the 
operating pressure to approximately 4-10 psi (0.23-0.67 kg/cm

2

) over desired 

mixed gas pressure. 

2.  If the LPG has a heavy end content, filters must be provided upstream of the 

regulator on the vapor inlet pipe to each 

BLENDAIRE

.  The user must 

determine the cleaning schedule for the filters.  A drip leg to drain the heavier 
particles should be provided immediately upstream of the first stage 
regulator. 

3.  Heat tracing must be placed over the vapor supply pipes if the ambient 

temperature falls within 10°F of the dewpoint of the LPG gas.  Electric heat 
tracing is preferred with an appropriate controller.  All heat tracing must be 
suitable for the class of hazardous location in which it is to be installed.  
Always consult with the appropriate authorities and all applicable codes. 

MIXED GAS OUTLET 

1.  The temperature of the pipe must be kept above the dewpoint of the air/gas 

mixture.  Heat tracing over the outlet pipe may be required as well. 

2.  A check valve must be installed in utility gas line if it is to be connected to 

utility gas main into plant. 

NOTE 

 

See the LPG gas dew points given in Appendix B 

 

 

 

PROCESS CONTROLLERS 

1.  The 

BLENDAIRE

 comes with a local PLC control panel suitable for 

hazardous area classification and a remote HMI panel suitable for General 
Location.   

2.  The 

BLENDAIRE

 utilizes 4-20mA, 24 VDC to provide power and 

communicate with the devices on the mixer. 120VAC is used to control safety 
solenoids on the mixer.  

3.  See wiring Diagram for wire type and required field connections. 

INSTRUMENT AIR SUPPLY 

1.  All safety shutoff valves and flow control valve operate on air and are closed 

when the air supply is cut off if a safety shutdown is triggered. 

2.  An instrument air regulator installed on the mixer must be supplied with 

clean, compressed instrument air of minimum 100 psi and no more than 150 
psi. 

 

Summary of Contents for Blendaire B1700

Page 1: ...intenance Manual Innovative liquid vaporizing and gas mixing solutions 151 South Michigan Street Seattle Washington USA 98108 Tel 206 789 5410 Fax 206 789 5414 Web www algas sdi com FILE MANUAL PN 54702 BLENDAIREII REV 11 30 16 doc ...

Page 2: ...contains manual shutoff valve check valve flow conditioner flow meter pressure transmitter and a flow control valve A required air regulator installed upstream sets the pressure into flow control valve The LPG vapor inlet piping contains manual shutoff valve check valve flow conditioner flow meter pressure transmitter and a safety shutoff valve A required LPG vapor regulator upstream sets the mixe...

Page 3: ...ntroduction 1 2 Algas SDI Operations and Maintenance Manual P N 54702 Figure 1 General Layout Figure 2 Component Diagram Compressed Air Inlet LPG Vapor Inlet SNG Outlet 10 6 1 3 7 4 5 8 11 2 6 1 7 5 4 9 ...

Page 4: ...sure Transmitter relays information to the remote control box to prevent low LPG pressure from forcing lean mixtures 7 TEMPERATURE TRANSMITTER The Temperature Transmitter determines if LPG gas vapor is at safe operating temperature The system will shut down if LPG vapor temperature is close to dewpoint The chart at the end of this section has the dewpoints for propane N butane and Isobutane 8 VAPO...

Page 5: ...the system at any time Heat tracing may be required depending upon location LPG content and pressure Mount each BLENDAIRE unit on a concrete pad strong enough to support its weight See equipment drawing Every unit is equipped with Auto Ratio Adjust however a gas quality measuring device suitable for the specific operating conditions is required for activation The total response time including samp...

Page 6: ...d be provided immediately upstream of the first stage regulator 3 Heat tracing must be placed over the vapor supply pipes if the ambient temperature falls within 10 F of the dewpoint of the LPG gas Electric heat tracing is preferred with an appropriate controller All heat tracing must be suitable for the class of hazardous location in which it is to be installed Always consult with the appropriate...

Page 7: ... in mind Various configurations allow inlets and outlet on same side of equipment on the opposite side of the equipment and 90 degrees apart from each other Figure 3 Inlets and Outlet on Same Side Figure 4 Inlets and Outlet on Opposite Sides Compressed Air Inlet LPG Vapor Inlet SNG Outlet Compressed Air Inlet LPG Vapor Inlet SNG Outlet ...

Page 8: ...Installation 3 8 Algas SDI Operations and Maintenance Manual P N 54702 Figure 5 Inlets and Outlet 90 Degrees Apart Compressed Air Inlet LPG Vapor Inlet SNG Outlet ...

Page 9: ...n in the gaseous state at all times The regulators will not operate properly if there is ANY liquid in the system Perform all necessary procedures to eliminate liquid in the system 5 Make adjustments to LPG and AIR regulators as required under flowing conditions Initial regulator settings can be found in the QA and Data Sheets BLENDAIRE MIXING RATIO ADJUSTMENT PROCEDURE Ratio adjustment is conduct...

Page 10: ...ding values To restart the blender after a safety shutdown determine and eliminate the cause of failure and begin the start procedure over 8 During initial startup of mixer into an uncharged line flow rates can be very high Alarms may occur during this charging phase until pressure in the line starts to equal the pressure outlet set point Also during this initial charging nuisance tripping of exce...

Page 11: ...essure upstream of the Air Flow Control Valve 2 Regulated LPG vapor pressure upstream of the Vapor Safety Shutoff Valve 3 Air and LPG Vapor flow rates 4 Calculated gas air mix ratio 5 Wobbe Index or specific gravity from Gas Quality Feedback Device SHUTTING DOWN THE BLENDER 1 Push the STOP button on the HMI panel or local control panel 2 Close the outlet valve 3 If the unit is to be serviced perfo...

Page 12: ...PG gas inlet valve to the mixer before performing any maintenance or repairs CAUTION Before performing any work on the blender follow all safety procedures for LPG gas make sure there are no open flames or electrical sparks and wear appropriate clothing Turn off all electrical power to the mixer ...

Page 13: ...Replace main valve seal Regulators Inspect and clean lines Clean upper body Clean and re build Safety Valve Perform visual inspection verify operation Rebuild actuator Replace main valve seal Pressure Transmitters Re calibrate verify operation Re calibrate verify operation replace as necessary PLC Controller Circuits Perform visual inspection verify operation PLC Controller Safeties Check Perform ...

Page 14: ...r shuts down on low gas pressure First stage gas regulator is set too low or is malfunctioning Increase gas pressure setting or check repair replace first stage gas regulator The pump pressure to the vaporizer is low or pump isn t functioning Check pump operation and incoming lines Vaporizer outlet valve is closed Open the valve Gas inlet shut off valve is closed Open the valve Vaporizer shuts dow...

Reviews: