background image

 

 

 

Algas-SDI Operations and Maintenance Manual – P/N – 54702

 

1-1

 

1. 

Introduction  

DESCRIPTION 

The 

BLENDAIRE

 is the ALGAS-SDI second generation “parallel pipe” design 

Synthetic Natural Gas (SNG) mixer.  The 

BLENDAIRE

 is designed to mix LPG 

vapor and air to simulate the combustion characteristics of natural gas.  During 
operation, the 

BLENDAIRE

 controls & responds to changes in discharge 

pressure due to consumption changes.  When operating in a piped network, as 
network pressure decreases, the SNG flow rate will increase to maintain 
pressure. Alternatively, when the network pressure rises, for example as 
consumption is reduced, the SNG flow will decrease.  The SNG discharge 
pressure is established by the LPG regulator installed upstream of the 

BLENDAIRE

.  LPG vapor and air flow rates are measured by flow meters. The 

ratio of these two flow rates is then compared to the calculated ratio of flow rates 
required to achieve a Wobbe value match to the natural gas being simulated.  
Adjustment of the ratio is made by adjusting the air flow only. As the flow of SNG 
increases or decreases, the Air Flow Control Valve modulates to maintain the 
correct and constant mixing ratio between the LPG and air.  

There are two separate flow paths into the 

BLENDAIRE

, one for air and one for 

LPG vapor, (See Figure 1).  The air inlet piping contains manual shutoff valve, 
check valve, flow conditioner, flow meter, pressure transmitter, and a flow control 
valve.  A required air regulator installed upstream sets the pressure into flow 
control valve.  The LPG vapor inlet piping contains manual shutoff valve, check 
valve, flow conditioner, flow meter, pressure transmitter, and a safety shutoff 
valve.  A required LPG vapor regulator upstream sets the mixed gas pressure at 
the outlet of the 

BLENDAIRE

.  The mixed gas line includes a static mixer 

section, safety shutoff valve, line pack pressure transmitter, and a manual shutoff 
valve (See Figure 2).  The line pack pressure transmitter automatically starts the 
mixer to an adjustable cut in pressure set point and maintains mixed gas 
pressure above this set point until desired line pressure is reached due to 
decreased demand.  

The 

BLENDAIRE 

utilizes a state-of-the-art PLC control technology designed by 

Algas-SDI to communicate with sensors and actuators and control the mixing 
ratio into the single gas line.  Adjustments to operating/control parameters are 
performed via the Human Machine Interface (HMI). 

The 

BLENDAIRE 

achieves extremely high accuracy and stability in the mixing 

process. Equally important, operation of the mixer is very simple. Once set up, 
the operation is fully automatic requiring minimum human intervention. 

In addition to high accuracy and stability, the 

BLENDAIRE

 maintains a high level 

of safety through the use of automatic safety shut-off valves and closure of the 
flow control valve. 

 

 

Summary of Contents for Blendaire B1700

Page 1: ...intenance Manual Innovative liquid vaporizing and gas mixing solutions 151 South Michigan Street Seattle Washington USA 98108 Tel 206 789 5410 Fax 206 789 5414 Web www algas sdi com FILE MANUAL PN 54702 BLENDAIREII REV 11 30 16 doc ...

Page 2: ...contains manual shutoff valve check valve flow conditioner flow meter pressure transmitter and a flow control valve A required air regulator installed upstream sets the pressure into flow control valve The LPG vapor inlet piping contains manual shutoff valve check valve flow conditioner flow meter pressure transmitter and a safety shutoff valve A required LPG vapor regulator upstream sets the mixe...

Page 3: ...ntroduction 1 2 Algas SDI Operations and Maintenance Manual P N 54702 Figure 1 General Layout Figure 2 Component Diagram Compressed Air Inlet LPG Vapor Inlet SNG Outlet 10 6 1 3 7 4 5 8 11 2 6 1 7 5 4 9 ...

Page 4: ...sure Transmitter relays information to the remote control box to prevent low LPG pressure from forcing lean mixtures 7 TEMPERATURE TRANSMITTER The Temperature Transmitter determines if LPG gas vapor is at safe operating temperature The system will shut down if LPG vapor temperature is close to dewpoint The chart at the end of this section has the dewpoints for propane N butane and Isobutane 8 VAPO...

Page 5: ...the system at any time Heat tracing may be required depending upon location LPG content and pressure Mount each BLENDAIRE unit on a concrete pad strong enough to support its weight See equipment drawing Every unit is equipped with Auto Ratio Adjust however a gas quality measuring device suitable for the specific operating conditions is required for activation The total response time including samp...

Page 6: ...d be provided immediately upstream of the first stage regulator 3 Heat tracing must be placed over the vapor supply pipes if the ambient temperature falls within 10 F of the dewpoint of the LPG gas Electric heat tracing is preferred with an appropriate controller All heat tracing must be suitable for the class of hazardous location in which it is to be installed Always consult with the appropriate...

Page 7: ... in mind Various configurations allow inlets and outlet on same side of equipment on the opposite side of the equipment and 90 degrees apart from each other Figure 3 Inlets and Outlet on Same Side Figure 4 Inlets and Outlet on Opposite Sides Compressed Air Inlet LPG Vapor Inlet SNG Outlet Compressed Air Inlet LPG Vapor Inlet SNG Outlet ...

Page 8: ...Installation 3 8 Algas SDI Operations and Maintenance Manual P N 54702 Figure 5 Inlets and Outlet 90 Degrees Apart Compressed Air Inlet LPG Vapor Inlet SNG Outlet ...

Page 9: ...n in the gaseous state at all times The regulators will not operate properly if there is ANY liquid in the system Perform all necessary procedures to eliminate liquid in the system 5 Make adjustments to LPG and AIR regulators as required under flowing conditions Initial regulator settings can be found in the QA and Data Sheets BLENDAIRE MIXING RATIO ADJUSTMENT PROCEDURE Ratio adjustment is conduct...

Page 10: ...ding values To restart the blender after a safety shutdown determine and eliminate the cause of failure and begin the start procedure over 8 During initial startup of mixer into an uncharged line flow rates can be very high Alarms may occur during this charging phase until pressure in the line starts to equal the pressure outlet set point Also during this initial charging nuisance tripping of exce...

Page 11: ...essure upstream of the Air Flow Control Valve 2 Regulated LPG vapor pressure upstream of the Vapor Safety Shutoff Valve 3 Air and LPG Vapor flow rates 4 Calculated gas air mix ratio 5 Wobbe Index or specific gravity from Gas Quality Feedback Device SHUTTING DOWN THE BLENDER 1 Push the STOP button on the HMI panel or local control panel 2 Close the outlet valve 3 If the unit is to be serviced perfo...

Page 12: ...PG gas inlet valve to the mixer before performing any maintenance or repairs CAUTION Before performing any work on the blender follow all safety procedures for LPG gas make sure there are no open flames or electrical sparks and wear appropriate clothing Turn off all electrical power to the mixer ...

Page 13: ...Replace main valve seal Regulators Inspect and clean lines Clean upper body Clean and re build Safety Valve Perform visual inspection verify operation Rebuild actuator Replace main valve seal Pressure Transmitters Re calibrate verify operation Re calibrate verify operation replace as necessary PLC Controller Circuits Perform visual inspection verify operation PLC Controller Safeties Check Perform ...

Page 14: ...r shuts down on low gas pressure First stage gas regulator is set too low or is malfunctioning Increase gas pressure setting or check repair replace first stage gas regulator The pump pressure to the vaporizer is low or pump isn t functioning Check pump operation and incoming lines Vaporizer outlet valve is closed Open the valve Gas inlet shut off valve is closed Open the valve Vaporizer shuts dow...

Reviews: