INSTALLATION & OPERATIONS GUIDE | MICROSET 4
© Honeywell LT-MS4IOG Rev. 04 | Revised October 2015
30
The after-hours timer automatically resets to zero if the zone is set to occupied (BV-64 ON).
Housekeeping Override (hotel mode):
After-hours operation (hotel mode)
The LCD displays the override time remaining. The unit controls to occupied setpoints while the
override timer (AV-98) is non-zero.
Housekeeping can press the
DOWN
arrow to cancel the override. The timer can’t restart until it has timed
down or been canceled.
Temperature screen
Press the left arrow to move
to the previous screen.
Press the right arrow to move
to the next screen.
Press the up arrow to set
the override timer to the
limit set in AV-97.
Override screen
is active.
Override timer
OVERRIDE
TIME
MIN SEC
0:00
CO
2
Press the up or down arrow
to increase or decrease the
temperature setpoint value.
Press the left arrow to move
to the previous screen, and
save changes made to the
setpoint value.
Press the right arrow to move
to the next screen, and
save changes made to the
setpoint value.
Cooling icon is displayed if
BV-78 is on.
Heating icon is displayed if
BV-77 is on.
Outside temperature.
Inside temperature.
Current setpoint value.
Temperature screen is
active.
TEMPERATURE
80
95
SET TO
72
CO
2
F
F
F