INSTALLATION & OPERATIONS GUIDE | MICROSET 4
Enabling operating modes
Combinations of values for BVs 64, 65, 80, and 81 control operating modes. In each mode, BV-67 (a
read-only point) reports occupied/unoccupied status. Use this data point in DDC as a flag to control
occupied and unoccupied operating sequences.
Table 6 lists data point settings for the various operating modes and indicates the action of BV-67 in
each mode. See Table 9 on page 49 for further detail.
Office modes
Office modes are typically used in commercial use environments. Screens might not appear on the
Microset 4 in the order shown, or at all, depending on Microset 4 model, configuration, and settings.
Table 6
Data point settings for Microset 4 operating modes, with BV-67 status.
MODE
DESCRIPTION
BV-64
OCCUPIED
BV-65
ON/OFF
BV-80
FAN-
CONTROL
BV-81
HOTEL
BV-67 (READ ONLY)
OCCUPIED/UNOCCUPIED
STATUS
M1
Office, no fan,
occupied
ON
OFF
OFF
OFF
ON
M2
Office, no fan,
unoccupied
OFF
OFF
OFF
OFF
OFF unless after-hours timer (AV-98)
is non-zero.
M3
Office, no fan, ON/
OFF
ON
ON
OFF
OFF
ON/OFF button on screen controls
BV-67 to match occupant selected
ON/OFF status.
M4
Office, fan,
occupied
ON
ON
a
a
The Microset turns BV-65 ON in these modes.
ON
OFF
BV-67 is ON when fan is on (BV72,
73, or 74 ON), OFF when fan is
AUTO
M5
Office, fan,
unoccupied
OFF
ON
a
ON
OFF
OFF unless after-hours timer (AV-98)
is non-zero.
M6
Hotel, no fan,
rented
ON
ON
a
OFF
ON
ON/OFF button on screen controls
BV-67 to match occupant selected
ON/OFF status.
M7
Hotel, no fan,
vacant
OFF
ON
a
OFF
ON
OFF unless housekeeping timer (AV-
98) is non-zero.
M8
Hotel, FC, Rented
ON
ON
a
ON
ON
BV-67 is ON when fan is on (BV72,
73, or 74 ON), OFF when fan is
AUTO
M9
Hotel, FC, Vacant
OFF
ON
a
ON
ON
OFF unless housekeeping timer (AV-
98) is non-zero.