16
Options Glossary
16
Defrost Modes
The frost control system is activated according to a reference temperature
or pressure (selectable option).
Built-in automated electric preheating coil (SSR-controlled).
Built-in liquid preheating coil (0 to 10V signal controls are available).
Face and bypass damper .
Built-in automated adjustable resistance clap (cool air diversion).
Defrost recirculation or exhaust cycles (see tables below for
temperature references).
All of the defrost modes listed below may not be included with your
device. Consult the specifications form provided with your device for more
information.
300952 V1.0
Tél. Can.: 1-800-262-0916 Usa.:1-800-255-7749
www.aldes.com
Sensible Fixed Plates recovery core (Alu. or Poly.)
°C
°F
Defrost Time
Ventilation
Time
T° > -5°C
T° > 23°F
N/A
Continuous
-25°C < T° < -5°C
-13°F < T° < 23°F
7 min
32 min
T° < -25°C
T° < -13°F
7 min
20 min
Sensible Fixed Plates recovery core (Enthalpy)
°C
°F
Defrost Time
Ventilation
Time
T° > -15°C
T° > 5°F
N/A
Continuous
-25°C < T° < -15°C
-13°F < T° < 5°F
7 min
32 min
T° < -25°C
T° < -13°F
7 min
20 min