3.2.6  Fault Outputs (Common Fault / AC Fault)

Form C Contacts

Contacts rated at 1A @ 24VDC, 0.5A @ 120VAC

Fault relays employ “fail-safe” operation and are powered in a non-fault condition (connection
between common and NO when no fault exists)

Each internal supply has independent sets of fault contacts

3.2.7  Distributed AC Outputs

Each distributed output is individually over-current protected (3A for fuse protected units,
1.6A for PTC protected units).

3.3 Fusing

When replacing fuses in the RMMV, only the equivalent type and rating are to be used.  The  RMMV
utilizes commonly available Automotive Miniature fuses (Type ATM).  Units whose model numbers
end in “F” employ ATM-3 fuses on the PCB located behind the front panel of the  RMMV.  An extra
fuse is provided on the bottom right corner of the PCB.

The internal PS5-M contains two replacable fuses - the Battery Fuse and the ABC Buss Fuse.  Both
fuses are rated at 15A (ATM-15).  The AC Input fuse is a soldered-in  non-replacable fuse.  If it is
determined that this fuse has opened, the PS5-M board must be returned to AlarmSaf for repair.

The internal SPS4 contains one replacable 7.5A (ATM-7.5) fuse.

RMMV Series Installation Instructions
7/13/2009, 10:26:56 AM

52-391 Rev A.02

Page 8 of 20

AlarmSaf

 65A Industrial Way, Wilmington, MA 01887 978 658 6717 www.alarmsaf.com

Summary of Contents for RMMV Series

Page 1: ...RMMV Series Rack Mount AC DC Power Supply Operating and Installation Instructions 52 391 Rev A 02...

Page 2: ...by customers by building vibration and by similar causes NOTICE This equipment is not intended for use within the patient care areas of a Health Care Facility NOTICE In order to comply with CSA Requir...

Page 3: ...1 Jumper Configuration 11 5 Operating the RMMV Rack Mount Power Supply 10 4 2 Wiring 9 4 1 Mounting 9 4 Installation 8 3 3 Fusing 7 3 2 Terminal Descriptions 6 3 1 Electrical Ratings and Specificatio...

Page 4: ...VDC or 24VDC by zone AC outputs are selectable for 24VAC or 28VAC by zone to overcome long wire runs Provide a green LED visual indicator for presence of output voltage by zone on the front panel Util...

Page 5: ...erence when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction...

Page 6: ...ones AC Zones Max Input Current Nominal Input Voltage Model Fuse Protected Products Note Maximum total DC load of 12V and 24V supplies must not exceed 4A maximum Current drawn from the 12V supply must...

Page 7: ...Part A095057 3 2 2 Distributed DC Outputs Out1 Out8 Each distributed output is individually over current protected 3A for fuse protected units 1 6A for PTC protected units Each output can be programm...

Page 8: ...utilizes commonly available Automotive Miniature fuses Type ATM Units whose model numbers end in F employ ATM 3 fuses on the PCB located behind the front panel of the RMMV An extra fuse is provided o...

Page 9: ...plied 10 32 X machine screws into the end brackets of the unit 4 1 2 Removing the faceplate of the unit To remove the faceplate of the RMMV Rack Mount Power Supply remove the four screws at the corner...

Page 10: ...block The back panel of the enclosure is labeled with the function and polarity or phase indications See also section 3 2 Replace the terminal block on the header and tighten the locking screws Figure...

Page 11: ...NUMBER DISCONNECT SUPPLY CORD BEFORE CHANGING FUSE DE BRANCHER AVANT DE REMPLACER LE FUSIBLE ATTENTION CAUTION Output Voltage Setting 5 1 2 DC Zones 5 1 2 1 Internal Jumper and Switch Configuration B...

Page 12: ...ult Settings Description Jumper 5 1 2 1 1 2 1 JP10 Bat Detect Battery Presence This jumper allows disabling of the battery presence detection for applications where no backup battery set is used 5 1 2...

Page 13: ...E REPLACE ONLY WITH SAME TYPE 3A 32V FUSE UTILISER UN FUSIBLE DE RECHANGE DE MEME TYPE 3 A 32 V V1 V2 V1 V2 REFER TO NAMEPLATE LABEL FOR INSTALLATION DOCUMENT REFERENCE NUMBER DISCONNECT SUPPLY CORD B...

Page 14: ...sual indicators Lights when the SPS4 detects a fault condition Yellow Fault FLT D6 Lights when DC voltage is present on the output Green DC Output DC OUT D8 Lights when DC voltage is present on the in...

Page 15: ...green output LEDs lit and no output voltages present Solution Possible Cause Condition 5 3 2 DC Section Troubleshooting Verify that individual and total output current is less than rated current Exces...

Page 16: ...orrect or Missing Battery Set Verify proper connection of the ABC cable s Improper ABC cable connection to the internal PS5 M Verify that output current is less than the rated current Excessive loadin...

Page 17: ...10 Zone Output Current 3A Fused or 1 6A PTC 6 1 11 Total DC Output Current 8A 4A 12VDC 24VDC 6 1 12 Total AC Output Current 12 5A 10A 24VAC 28VAC 6 2 Temperature Specifications 6 2 1 Ambient Temperatu...

Page 18: ...TO EACH BAT SET For complete information read Installation Instruction manual 52 342 or internal label 12V 24V Battery Set 1 Configuration OR VOLTAGE SELECTION Configuring the Rear Panel Jumpers on t...

Page 19: ...unt Power Supply Wiring between the RMBE and RMMV must be sized appropriately for the maximum current The terminal strips on the RMBE will accept AWG 12 26 Each battery set has two parallel outputs bo...

Page 20: ...erters allow multi voltage system backup with a single battery set DC DC Converter Voltage distribution providing on off control for the outputs Control can be from FAI an access control panel card re...

Reviews: