5.1.2.1.2 SPS4 Jumper Settings
The SPS4 has two jumpers for setting its output voltage. It is factory set for 12VDC out. If
a different voltage is required, the jumpers must be changed as follows:
Left
Right
5-18VDC Adjustable*
Right
Left
12VDC
Left
Left
5VDC
JP2
JP1
Voltage Output
* - When using the adjustable range, adjust the output voltage using potentiomer R5
5.2 Visual Indicators
5.2.1 External Visual Indicators
5.2.1.1 Illuminated Power Switch / Circuit Breaker
The power switch will illuminate red when the power switch is in the “on” position and power
is present.
5.2.1.2 Front Panel Indicators
All units have front panel indicator LEDs. Each output has one LED which illuminates when
voltage is available at the corresponding output terminals.
F
1
7
D1
D2
D3
D4
D5
D6
D7
D8
D9
D10
D11
D12
D13
D14
D15
D16
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
F15
F16
J1
J2
JP1
JP2
JP3
JP4
JP5
JP6
JP7
JP8
JP9
JP10
JP11
JP12
JP13
JP14
JP15
JP16
J3
J4
J5
J6
J7
J8
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
32V
3A
SPARE
38-124 Rev B
1
1
ZONES 9 - 16
ZONES 1 - 8
FOR CONTINUED PROTECTION AGAINST RISK OF FIRE
REPLACE ONLY WITH SAME TYPE 3A. 32V FUSE.
UTILISER UN FUSIBLE DE RECHANGE
DE MEME TYPE 3 A 32 V
V1
V2
V1
V2
REFER TO NAMEPLATE LABEL
FOR INSTALLATION DOCUMENT
REFERENCE NUMBER
DISCONNECT SUPPLY CORD BEFORE
CHANGING FUSE
DE'BRANCHER AVANT DE REMPLACER LE FUSIBLE
ATTENTION:
CAUTION:
Visual Indicators (D1-D16)
5.2.2 Internal Visual Indicators
5.2.2.1 Indicators on the internal PS5-M Board
The PS5-M contains five visual status indicators.
Lights under an Earth Ground Fault condition
Yellow
Earth Ground Fault
GND FLT (D23)
See Section 5.2.2.1.4
Yellow
Common Fault
COM FLT (D16)
Lights when the AC input voltage is low or missing
Yellow
AC Fault
AC FLT (D22)
Lights when DC voltage is present on the output
Green
DC Output
DC OUT (D15)
Lights when AC voltage is present on the input
Green
AC Power
AC ON (D19)
Conditions
Color
Description
LED
5.2.2.1.1 AC ON
For safety reasons, this LED illuminates any time there is AC voltage present at the AC
input, regardless of the AC fault status, battery state of charge, or power supply condition.
CAUTION - Always check for AC presence with a volt meter before servicing
5.2.2.1.2 DC OUT
This LED illuminates when DC voltage is available at the DC+/DC- terminals.
RMMV Series Installation Instructions
7/13/2009, 10:26:56 AM
52-391 Rev A.02