5
2. When the lock is disarmed, pressing the bar or paddle will
open the door instantly without sounding the alarm. Check
that the lock relatches after 5 seconds.
3. Trip the fire-detection or other emergency device with the
lock armed. Press the bar or paddle and check that the
latch is released instantly and that the alarm sounds. The
smoke detector is reset by disarming the lock.
4. The unit is electrically failsafe. Should any wire open for
any reason, the exit delay will be eliminated and the door
may be exited by pressing the bar or paddle.
Low-Battery Indication
A low-battery condition will be indicated by a “chirp” from
the sounder about once each minute. Be sure to replace
the battery promptly. An alkaline replacement is strongly
recommended for optimum reliability and length of
service.
Lubrication
These models are designed to provide many years of
reliable service when lubricated periodically. Inspect the
lock on a routine basis in accordance with anticipated use.
Replenish the factory-applied lubricants at least every five
years or 25,000 operations, whichever occurs first, using
the specified lubricants at the points shown in the Wiring
Diagram.
EXPLODED VIEW AND PARTS LIST, MODEL 265