OUTPUT MODE & TIMING FOR OUTPUT 1 (Function 51)
Enter Programming Mode by entering Program Code and * *
The keypad output is programmable for Start/Stop or Timing modes. Apart from door access
control, alarm arm-disarm control, there is also an
universal timers for automatic operators
with
up to 99,999 seconds (over 24 hours) of programmable unlock time.
(1) FUNCTION
-- Function for Output 1
(2) OUTPUT MODE & TIMING
Toggle Mode
The number 0 sets the output to
Toggle mode
. The output
Starts
when an User Code is entered;
the output
Stops
when an User Code is entered again. Note: This is similar to the function of the
Supervisor code, but now “ALL” User Codes will toggle the output relay.
--
Seconds Momentary --- (Default -- Momentary 5 Seconds)
The output can be set in
Momentary Mode
with the time of 1 second to 99,999 seconds. The
output will reset automatically when the time expires.
(3) VALIDATION
Press key once. Two-Echo Tones confirms the entry.
When finished Press * * to exit Programming Mode.
RESET OUTPUT TIMER WITH SUPERVISOR CODE
If you have a extremely long time set on the Output Timer it can be
RESET manually at anytime
with the Supervisor Code
that operates the output before the end of the time. This procedure can
take the keypad out of Toggle Mode.
Example:
Reset Output Relay Timer
--
----------
Output Relay stops
SUPERVISOR CODE
OUTPUT MODE & TIME
VALIDATION
FUNCTION
51
0
or
1
-
99999
#
(3)
(2)
(1)