Alarko Carrier AIROStar 39SQ Installation, Operation And Maintenance Instructions Download Page 21

21

• Check for possible condensate/moisture. Condensate 

may form in the period before the first start-up of the 
AHU as a result of weather change and/or humid air 
from the building. Remove all condensate from the 
construction components and dry the electrical 
components using warm (dry) air (e.g. with a hair 
drier).

• Check the supply
• The unit supply must be protected by a correctly sized 

fuse.

• Connect all external sensors, control devices and 

external controls to the terminal board as shown in the 
wiring diagram supplied.

• If required include alarms, release signals and similar 

elements in the BMS or on the external panel.

• Set the controller for the specific project parameters, 

such as operating times, holidays etc. Follow the 
instructions given in the operating instructions for the 
“Pro Dialog AHU control”.

• The control panel is ventilated using exhaust air. To 

ensure the air flow there is a grille in the control panel 
hatch. This must not be covered.

• The control panel hatch must be locked when the AHU is 

started.

CAUTION: If the AHU includes an electric heater, the
heater needs to have a separate power supply.

4.14 - Installation of external sensors included

Outdoor air temperature sensor

The passive PT1000 sensor must be 
installed outside on a wall with north 
exposure. Ensure that the gland is at 
the bottom. This sensor (if required) is 
supplied separately and must be 
connected to the control panel after 
the unit has been installed. In the 
control diagram this sensor is shown 
as 23TT22 (TT6). 

Room temperature sensor

The passive PT1000 sensor includes 
room temperature correction with 
regard to the required setpoint. The 
sensor must be positioned in the 
representative room and not be 
exposed to direct sunlight and not be 
near a local heat source.
This sensor (if required) is supplied 

separately and must be connected to the control panel 
after the unit has been installed. In the control diagram this 
sensor is shown as 24TT4 (TT5).

Duct pressure sensor

The active sensor (24 V) has a 
maximum measurement range of up 
to 3000 Pa.

This sensor (if required) is supplied 
separately and must be connected 
to the control panel after the unit has 
been installed. In the control diagram 

this sensor is shown as 25PDT13 (PT3). The sensor cannot 
be placed in the outdoor air.

The “+” pressure measurement point must be in a 
representative and stable position in the supply air of the 
duct system (not directly after a damper, bend, branch or 
similar). The “–“ pressure measurement point can measure 
atmospheric pressure in the room.

CO

2

 sensor

The active sensor (24 V) must be 
placed in the correct room in a location 
that is representative of the CO

2

 

concentration in the room. Connect 
terminal 7 - 8 in the CO

2

 sensor to the 

correct terminal at the terminal strip in 
the control panel.

This sensor (if required) is supplied separately and must be 
connected to the control panel after the unit has been 
installed. In the control diagram this sensor is shown as 
25QT22(QT)

Summary of Contents for Carrier AIROStar 39SQ

Page 1: ...39SQ 39SQR 39SQP Airostar Air Handling Units Installation operation and maintenance instructions...

Page 2: ...an 16 4 11 Silencers 19 4 12 Lighting 19 4 13 Control panel 20 4 14 Installation of external sensors included 21 4 15 Sensor Replecament 22 5 MAINTENANCE CHECKLIST 23 5 1 Checklist of check points and...

Page 3: ...guidelines of the Pressure Equipment Directive PED Do not walk on the roof panels of units installed inside or outside Technical staff who is responsible for startup and maintanence has to take occupa...

Page 4: ...tted to carry out work on these components Do not work on electrical components including control panels switches VFD untill you are sure ALL POWER IS OFF and no residual voltage can leak from capacit...

Page 5: ...ple in the immediate vicinity of the unit are endangered Carrier does not accept any responsibility if these instructions are not observed Transport and lifting must be carried out by qualified person...

Page 6: ...mended for direct drive fans 2 6 Warranty The units will 2 years warranty after invoice date if startup storage and maintenance are made according to this manuel 2 7 Placement The unit have to be plac...

Page 7: ...t recovery wheel I Recirculation damper J Supply air fan K Extract air filter L Electric reheater hot water M Cooling coil with changeover N Supply air damper O Extract air damper Legend 1 Actuator ou...

Page 8: ...ypass damper H Control panel I Supply air fan J Extract air fan K Electric reheater hot water L Cooling coil with changeover M Supply air damper N Exhaust air damper Legend 1 Actuator outdoor air extr...

Page 9: ...er end position Filters Correct filter type Are the filters correctly installed Pressure differential gauge Correct operation Pressure differential switch Correct operation set up Heaters Hot water co...

Page 10: ...of a single skin flexible connection is 170 mm but a flexible connection must NOT be installed stretched between the AHU and the duct Once installed the operating length of the flexible connection mus...

Page 11: ...to prevent that mist causes the filters to become too wet The pre heater will reduce the relative humidity of the air Connection of the outdoor air intake duct If condensation can be expected in or o...

Page 12: ...further apart using an extra piece of duct at the outdoor air intake opening If the units are installed outside this piece of duct should be placed between the air handling unit and the pre installed...

Page 13: ...e moisture Condensate may form in the period before the first start up of the AHU as a result of weather change and or humid air from the building Remove all condensate from the construction component...

Page 14: ...pump the installation must be designed to compensate for the required heat during the system heat pump defrost cycle and the heat cannot be drawn from the supply air Otherwise the supply air temperatu...

Page 15: ...is best to use an infinitely variable controller for the compressor condensing unit If the condensing unit has infinitely variable control one of the temperature controls in the controller can be sele...

Page 16: ...heat recovery wheel is supplied with rotor control included in the central control panel The rotation monitor for the rotor is pre installed and connected If required the heat recovery wheel can incl...

Page 17: ...cked open This warning also important for safety Because of the positive pressure fan doors can hit the technical personel who is opening the doors Before openning the doors the fan must be switched o...

Page 18: ...n can rotate depends on the motor impeller assembly and should normally be higher than 50 Hz The maximum frequency is given on the fan name plate Plug fans are equipped with a pressure measurement poi...

Page 19: ...from the building Remove all condensate from the construction components and dry the electrical components using warm dry air e g with a hair drier Do not work on electrical components including contr...

Page 20: ...32 32 16 63 63 63 63 100 100 1 260 1 260 1 260 1 260 2 000 2 000 5 5 5 5 5 5 7 5 7 5 11 5 5 7 5 11 7 5 11 11 32 40 63 40 63 63 4 32 32 32 640 640 640 1 1 1 1 2 2 1 1 2 2 2 2 16 16 25 4 32 32 32 32 63...

Page 21: ...connected to the control panel after the unit has been installed In the control diagram this sensor is shown as 23TT22 TT6 Room temperature sensor The passive PT1000 sensor includes room temperature...

Page 22: ...ol damper will open if the water temperature measured is below 20 C Heating mode detection if the measured water temperature is higher than the sum of the setting values at the bottom and top dials se...

Page 23: ...inspections and maintenance of the AHU On the following pages there is a more detailed description of the individual components WARNING Remember to deenergise all components and to ensure that the fan...

Page 24: ...installed in the correct manner 6 6 Dampers Lubrication of the dampers is not required Remove excess contamination by cleaning with compressed air and possible cleaning with water and a mild household...

Page 25: ...Heat recovery wheel Check the rotor once a year for contamination and if necessary clean with compressed air Check the rotor speed and compare it with the design data Check the operation of the rotati...

Page 26: ...gn of bearing wear but also of incorrect operation of the transmission or an unbalanced system The following points require extra attention Check for vibration Check the rotation direction Avoid unnec...

Page 27: ...Silencers It is recommended to check the splitters of the silencers periodically for possible damage and loosening of the fibres to prevent dirt deposits in the system 6 16 Control The control must b...

Page 28: ...ERE THE AHU S POWER SUPPLY FIND THE SWITCH WHICH BELONGS TO AHU S POWER SUPPLY OPEN THE SWITCH 5 PUT THE LOCK BACK NOTE AT THE 3 STAGES SWITCHES 2 AUTOMATION 1 MANUEL CONTROL 0 MEANS CLOSE PINBOARD PI...

Page 29: ...NOT TOUCH THE PIPES 4 CLOSE THE ELECTRICAL HEATER MAIN SWITCH SWITCH WILL BE SET FROM 1 TO 0 POSITION LOCK THE ELECTRICAL HEATER MAIN ELECTRIC SWITCH 5 CLOSE THE MAIN HEATER WATER VALVE CLOSE THE MAI...

Page 30: ...Order No 13938 11 07 2016 Supersedes order No 13938 11 07 2014 Manufactured by Alarko Carrier Gebze Turkey The manufacturer reserves the right to change the specification without prior notice...