11

• 

To be able to make two openings one above the other 
the corner frames of the two openings have a different 
length so that there is always enough space to place 
and attach the profiles. Using the drive slip means that 
there is no need to use screws in the limited space 
between the two ducts that are one above the other, 
as shown in the drawing below.

• 

The corner frame has a length of 32 or 72 mm and 
extends 22 or 62 mm beyond the external AHU 
dimension, as shown in the drawing below.

• 

The flexible connection, including the installed corner 
frame, extend 170 mm beyond the external AHU 
dimension, and a damper set 132/172 or 207/247 
mm, as shown in the drawing below.

Legend
1. AHU
2. Flexible connection or damper

3. Duct connection

(single-skin flexible connection - ± 30 mm press fit)

• 

The combination of flexible connections and dampers, 
including the installed corner frame, extends 302/337 
or 342/417 mm beyond the external AHU dimension, 
as shown in the drawing below.

If these can be expected for the installation or geographical 
location, try to minimise them with partitions. If there is any 
possibility that rain water can be drawn in, droplet 
eliminators must be added behind the air intake grille. A 
pre-heater for the filters can be installed to prevent that 
mist causes the filters to become too wet. The pre-heater 
will reduce the relative humidity of the air.

Connection of the outdoor air intake duct

If condensation can be expected in or on the ducts, these 
must be insulated on the outside.

To connect the outdoor air intake duct to a unit that is 
installed inside we recommend the following procedure:
•   Connect a 500 mm long adapter piece to the corner 

frame of the air handling unit.

•   Insulate the inside of the complete adapter piece up to 

the unit panel.

•   Insulate the outside of the adapter piece so that there 

is a 250 mm overlap between inside and outside 
insulation.

•   The remainder of the adapter piece needs to be 

insu-lated on the outside, as shown in the drawing 
below.

4.1.6 - Outdoor air intake

• 

Ensure that the air intake duct is correctly connected. 
High air velocities must be avoided and no rain drops 
should get into the duct. This can be prevented by 
installing rain protec-tion air intake grilles (Caution: The 
maximum air velocity for the grille is as given by the 
supplier). The rear air intake duct must be sized to 
avoid higher than allowable air veloci-ties in the grille. 
High air velocities in the openings can also be caused 
by wind attacks at one of the openings.

(single-skin flexible connection - ± 30 mm press fit)

Legend
1. AHU
2. Duct connection

Legend
1. AHU
2. Damper

3. Flexible connection
4. Duct connection

302/337 or 342/417 mm

170 mm

132/172 or 207/247 mm

22/62 mm

Summary of Contents for Carrier AIROStar 39SQ

Page 1: ...39SQ 39SQR 39SQP Airostar Air Handling Units Installation operation and maintenance instructions...

Page 2: ...an 16 4 11 Silencers 19 4 12 Lighting 19 4 13 Control panel 20 4 14 Installation of external sensors included 21 4 15 Sensor Replecament 22 5 MAINTENANCE CHECKLIST 23 5 1 Checklist of check points and...

Page 3: ...guidelines of the Pressure Equipment Directive PED Do not walk on the roof panels of units installed inside or outside Technical staff who is responsible for startup and maintanence has to take occupa...

Page 4: ...tted to carry out work on these components Do not work on electrical components including control panels switches VFD untill you are sure ALL POWER IS OFF and no residual voltage can leak from capacit...

Page 5: ...ple in the immediate vicinity of the unit are endangered Carrier does not accept any responsibility if these instructions are not observed Transport and lifting must be carried out by qualified person...

Page 6: ...mended for direct drive fans 2 6 Warranty The units will 2 years warranty after invoice date if startup storage and maintenance are made according to this manuel 2 7 Placement The unit have to be plac...

Page 7: ...t recovery wheel I Recirculation damper J Supply air fan K Extract air filter L Electric reheater hot water M Cooling coil with changeover N Supply air damper O Extract air damper Legend 1 Actuator ou...

Page 8: ...ypass damper H Control panel I Supply air fan J Extract air fan K Electric reheater hot water L Cooling coil with changeover M Supply air damper N Exhaust air damper Legend 1 Actuator outdoor air extr...

Page 9: ...er end position Filters Correct filter type Are the filters correctly installed Pressure differential gauge Correct operation Pressure differential switch Correct operation set up Heaters Hot water co...

Page 10: ...of a single skin flexible connection is 170 mm but a flexible connection must NOT be installed stretched between the AHU and the duct Once installed the operating length of the flexible connection mus...

Page 11: ...to prevent that mist causes the filters to become too wet The pre heater will reduce the relative humidity of the air Connection of the outdoor air intake duct If condensation can be expected in or o...

Page 12: ...further apart using an extra piece of duct at the outdoor air intake opening If the units are installed outside this piece of duct should be placed between the air handling unit and the pre installed...

Page 13: ...e moisture Condensate may form in the period before the first start up of the AHU as a result of weather change and or humid air from the building Remove all condensate from the construction component...

Page 14: ...pump the installation must be designed to compensate for the required heat during the system heat pump defrost cycle and the heat cannot be drawn from the supply air Otherwise the supply air temperatu...

Page 15: ...is best to use an infinitely variable controller for the compressor condensing unit If the condensing unit has infinitely variable control one of the temperature controls in the controller can be sele...

Page 16: ...heat recovery wheel is supplied with rotor control included in the central control panel The rotation monitor for the rotor is pre installed and connected If required the heat recovery wheel can incl...

Page 17: ...cked open This warning also important for safety Because of the positive pressure fan doors can hit the technical personel who is opening the doors Before openning the doors the fan must be switched o...

Page 18: ...n can rotate depends on the motor impeller assembly and should normally be higher than 50 Hz The maximum frequency is given on the fan name plate Plug fans are equipped with a pressure measurement poi...

Page 19: ...from the building Remove all condensate from the construction components and dry the electrical components using warm dry air e g with a hair drier Do not work on electrical components including contr...

Page 20: ...32 32 16 63 63 63 63 100 100 1 260 1 260 1 260 1 260 2 000 2 000 5 5 5 5 5 5 7 5 7 5 11 5 5 7 5 11 7 5 11 11 32 40 63 40 63 63 4 32 32 32 640 640 640 1 1 1 1 2 2 1 1 2 2 2 2 16 16 25 4 32 32 32 32 63...

Page 21: ...connected to the control panel after the unit has been installed In the control diagram this sensor is shown as 23TT22 TT6 Room temperature sensor The passive PT1000 sensor includes room temperature...

Page 22: ...ol damper will open if the water temperature measured is below 20 C Heating mode detection if the measured water temperature is higher than the sum of the setting values at the bottom and top dials se...

Page 23: ...inspections and maintenance of the AHU On the following pages there is a more detailed description of the individual components WARNING Remember to deenergise all components and to ensure that the fan...

Page 24: ...installed in the correct manner 6 6 Dampers Lubrication of the dampers is not required Remove excess contamination by cleaning with compressed air and possible cleaning with water and a mild household...

Page 25: ...Heat recovery wheel Check the rotor once a year for contamination and if necessary clean with compressed air Check the rotor speed and compare it with the design data Check the operation of the rotati...

Page 26: ...gn of bearing wear but also of incorrect operation of the transmission or an unbalanced system The following points require extra attention Check for vibration Check the rotation direction Avoid unnec...

Page 27: ...Silencers It is recommended to check the splitters of the silencers periodically for possible damage and loosening of the fibres to prevent dirt deposits in the system 6 16 Control The control must b...

Page 28: ...ERE THE AHU S POWER SUPPLY FIND THE SWITCH WHICH BELONGS TO AHU S POWER SUPPLY OPEN THE SWITCH 5 PUT THE LOCK BACK NOTE AT THE 3 STAGES SWITCHES 2 AUTOMATION 1 MANUEL CONTROL 0 MEANS CLOSE PINBOARD PI...

Page 29: ...NOT TOUCH THE PIPES 4 CLOSE THE ELECTRICAL HEATER MAIN SWITCH SWITCH WILL BE SET FROM 1 TO 0 POSITION LOCK THE ELECTRICAL HEATER MAIN ELECTRIC SWITCH 5 CLOSE THE MAIN HEATER WATER VALVE CLOSE THE MAI...

Page 30: ...Order No 13938 11 07 2016 Supersedes order No 13938 11 07 2014 Manufactured by Alarko Carrier Gebze Turkey The manufacturer reserves the right to change the specification without prior notice...

Reviews: