Operation

The thermostat communicates with the wireless damper 
actuator via an RF wireless data link.  It monitors the space 
temperature and the setpoint temperature and sends data to 
the damper telling it how many degrees the space temperature 
is above or below the temperature setting. 

The actuator has a temperature sensor that monitors the 
supply air temperature to determine if the HVAC system is or 
has been calling for heating or cooling. The damper then 
opens or closes proportional to the temperature differential it 
received from the thermostat.

The thermostat periodically adjusts the airflow. The interval 
can be set from 5 to 30 minutes. The change in airflow can be 
set to either 8% or 16% per degree of temperature differential.

Energy Savings

The wireless thermostat and damper are used to automatically 
control airflow to maintain a comfortable temperature and 
eliminate the annoying overcooling and overheating found in 
many work areas, offices, restaurants and other spaces.

Excess airflow that caused the overcooling or overheating is 
automatically redirected to areas that need it and the 
thermostat is satisfied sooner, resulting in less operating time 
for the HVAC system.

The thermostat has an Off position that can shut the airflow 
down when the office or space is not being used and provide 
even greater energy savings. The night setback feature works 
the same way and provides added energy savings.

Improved Comfort

The WCD Damper actuator has a Close position limit that can 
be used to insure a minimum airflow even when the thermostat 
tries to fully close the damper. The minimum Close position 
can be set from about 50% closed to fully closed.

This should be used when a large number of WCD Dampers 
are used with the same HVAC system to insure that static 
pressure does not damage the ducts.

See the Installation Instructions supplied with the WCD 
Damper for setting the Close position limit.

Mechanical Bypass

1

Close Cam

Set Screw

Cam Cover

Hold the sub-base with one hand, press the case as shown 
below and pull the bottom of the thermostat from the sub-base.

Press here to release 

case from sub-base.

Before Installation

Remove the Sub-base

2

The thermostat can be installed on any interior wall 
approximately 5 feet above the floor. To insure accurate 
reading of the space temperature, the thermostat should not be 
in direct sunlight.

Install the sub-base using two #8 or #6 sheet metal screws 
with wall anchors where required.  Level the thermostat for 
appearance.

Installing the Sub-Base

3

Slide the battery cover off and 
install two AA lithium or alkaline 
batteries.  Install the batteries 
with the positive terminals to 
the right as shown.  Replace 
the battery cover.

Installing the Batteries

4

Summary of Contents for T200WL01

Page 1: ...le Mode Hold Mode System Modes LCD Backlight Wireless Control Automatically controls airflow based on temperature setting space temperature and supply air temperature Temperature sensor at the WCD damper senses heating or cooling calls WCD Dampers A80 WL Wireless Actuator 100 to 0 or minimum airflow set by mechanical stop on the actuator 1 zone can control up to 32 different dampers 32 different a...

Page 2: ...n Off position that can shut the airflow down when the office or space is not being used and provide even greater energy savings The night setback feature works the same way and provides added energy savings Improved Comfort The WCD Damper actuator has a Close position limit that can be used to insure a minimum airflow even when the thermostat tries to fully close the damper The minimum Close posi...

Page 3: ... be set from 1 to 32 Press the Next key to advance to the next option Press the Enter key if no more options are to be changed Or press the Cancel key to exit the option sequence and return to normal operation Option Zone CANCEL NEXT ENTER Option 01 Setting Zone Number Default 01 601 The Home address is used to distinguish between installations that are less than 500 feet away This allows neighbor...

Page 4: ...user can set Use the Next key to select Option 07 Use the Up and Down keys to set the High Setpoint Limit The limit can be set from 60 to 90 degrees Set High Setpoint Limit Default 80 Degrees 607 Option CANCEL NEXT ENTER The Low Setpoint Limit is the lowest setpoint temperature the user can set Set Low Setpoint Limit Default 65 Degrees 608 Option Zone Home CANCEL NEXT ENTER Use the Next key to sel...

Reviews: