Installer options can be accessed by pressing and holding the 
unmarked key below the System key for seven seconds. The
LCD will display Option 01 for setting the Zone number.

Press or hold the Next key to advance to the next option. The
LCD will advance to Option 11 and return to Option 01.  Press 
the Cancel key to exit the option selections.  Press the Enter 
key to save all options in non-volatile flash ram.

Option

Description

Zone number
Range

Range

Range

Range

Range

Range

Range

Range

Range

Range

1 to 32

1 to 32

o

1 to 5 F

o

60 to 90 F

o

55 to 80 F

0 to 100%

0 to 100%

0- 8%/F  1-16%/F

5 to 30 minutes

0- On with key

Default

1

1

na

o

1 F

o

80 F

o

65 F

50%

50%

0- 8%/F

10 minutes

On with key stroke

Address number

Program Damper with Zone 
and Home address

Dead-band Differential

Update interval

LCD back-light control

High setpoint limit

Low setpoint limit

Damper factor

Night airflow

Off airflow

01

02

03

04

05

06

07

08

09

10

11

Accessing the 

Installation Options

5

3

If only one wireless thermostat is used in the installation, the 
default Zone 01 and Home 01 can be used.  Skip to setting 
Option 04. If multiple wireless thermostats are used, each 
thermostat and module have to be programmed with a unique 
Zone number. The first thermostat can use the factory set 
Zone 01 and Home 01 address.

Use the Up and Down keys to set the Zone number for the 
other thermostats. The Zone number can be set from 1 to 32.

Press the Next key to 
advance to the next option.
Press the Enter key if no 
more options are to be 
changed. Or press the 
Cancel key to exit the 
option sequence and return 
to normal operation.

Option

Zone

CANCEL NEXT

ENTER

Option 01 Setting Zone Number

Default= 01

6

01

The Home address is used to distinguish between installations 
that are less than 500 feet away. This allows neighbors, 
different departments or floors to use the wireless thermostats 
and not interfere with each other.  Skip to Setting Option 04 if 
no other user groups are nearby.

Use the Next key to select Option 02.  Use the Up and Down 
keys to set the Home number for this thermostat. The Home 
number can be set from 1 to 8.  If multiple departments are 
installing wireless thermostats, each department should use a 
different Home number to insure a WCD Damper in another 
department is not inadvertently changed.

Option

Home

CANCEL NEXT

ENTER

Setting Home Number

Default= 01

6

02

After selecting the Zone and Home numbers for the 
thermostat, the same address must be set into the WCD 
Damper actuator.  First press the Program key on the actuator.
The actuator will accept a new address for thirty seconds. The
LED will alternately blink red and green while it is waiting for a 
new address. Wireless damper actuators are shipped with 
default address Zone=1 and Home=1.

Programming Wireless Damper

6

03

The LCD display for Option 03 is shown below.  Press the 
Enter key to send the new address to the WCD Damper 
actuator. The damper will now only respond to the thermostat 
with the same address.

Option

Zone

CANCEL NEXT

ENTER

Press switch to enable 
programming Zone 
and Home number.

COM

24VAC

GND

VP

TS

Summary of Contents for T200WL01

Page 1: ...le Mode Hold Mode System Modes LCD Backlight Wireless Control Automatically controls airflow based on temperature setting space temperature and supply air temperature Temperature sensor at the WCD damper senses heating or cooling calls WCD Dampers A80 WL Wireless Actuator 100 to 0 or minimum airflow set by mechanical stop on the actuator 1 zone can control up to 32 different dampers 32 different a...

Page 2: ...n Off position that can shut the airflow down when the office or space is not being used and provide even greater energy savings The night setback feature works the same way and provides added energy savings Improved Comfort The WCD Damper actuator has a Close position limit that can be used to insure a minimum airflow even when the thermostat tries to fully close the damper The minimum Close posi...

Page 3: ... be set from 1 to 32 Press the Next key to advance to the next option Press the Enter key if no more options are to be changed Or press the Cancel key to exit the option sequence and return to normal operation Option Zone CANCEL NEXT ENTER Option 01 Setting Zone Number Default 01 601 The Home address is used to distinguish between installations that are less than 500 feet away This allows neighbor...

Page 4: ...user can set Use the Next key to select Option 07 Use the Up and Down keys to set the High Setpoint Limit The limit can be set from 60 to 90 degrees Set High Setpoint Limit Default 80 Degrees 607 Option CANCEL NEXT ENTER The Low Setpoint Limit is the lowest setpoint temperature the user can set Set Low Setpoint Limit Default 65 Degrees 608 Option Zone Home CANCEL NEXT ENTER Use the Next key to sel...

Reviews: