5. Assembly
Warning!
Installation, electrical connection, media supply connection, maintenance, commissioning, repair, etc. may only
be performed by trained staff.
The place of installation as well as the installation structure must provide permanent and vibration-free support of
the devices.
The place of installation and the installation structure has to be checked by a structural engineer, if required.
AL-KO air heaters are delivered in pre-assembled form.
The manufacturer documentation must be considered before installation or removal.
The air heaters must be levelled during the installation!
5.1
Ceiling installation of the devices
Device Version K
The Device Version K is intended for low rooms. The recirculated air is sucked in at the bottom centre of the device. The
heated air is distributed in four directions. The outlet louvres should be directed slightly downwards. The air heater can
either be mounted directly under the ceiling or fastened at a distance to the ceiling with Console Set a or c (optional).
Max. permitted distance from the floor to the bottom edge of the device:
Type 140-K
=
2400 mm
Type 250-K
=
2500 mm
Type 400-K
=
2700 mm
Type 650-K
=
3400 mm
Device Version K/h
The K/h device version is intended for medium-high rooms. The recirculated air is taken in at the ceiling on all four sides,
heated and blown downwards into the room in a cone-shaped stream. The air heater can either be mounted directly
under the ceiling or fastened at a distance to the ceiling with Console Set a or c (optional).
Max. permitted distance from the floor to the bottom edge of the device:
Type 140-K/h =
3500 mm
Type 250-K/h =
4000 mm
Type 400-K/h =
4500 mm
Type 650-K/h =
5000 mm
Device Version K/o
The K/o device version is intended for low rooms. The recirculated air is sucked in at the centre top of the device. The
heated air is distributed in four directions. The outlet louvres should be directed slightly downwards. The air heater must
be mounted to leave at least a distance of 150 mm from the fan to the ceiling. Console set a (optional) can be used for
this purpose.
Max. permitted distance from the floor to the bottom edge of the device:
Type 140-K/o =
2400 mm
Type 250-K/o =
2500 mm
Type 400-K/o =
2700 mm
Type 650-K/o =
3400 mm
"Assembly"