AL-KO air heater / air cooler DESIGN
5.5.1 Fan
Check the rotation direction of the fan.
The rotation direction must correspond with the rotation direction arrow on the fan blade or the fan housing.
Technical data of fan:
Type
BS 1
BS 2
BS 3
Operating voltage
in V
3~400 V/50 Hz
3~400 V/50 Hz
3~400 V/50 Hz
Power uptake
in kW
0.11
0.07
0.22
0.13
0.36
0.22
Nominal current in A
0.27
0.13
0.56
0.29
0.83
0.46
Operating speed
rpm
900
750
900
680
890
630
Insulation class
THCL 155 (F)
THCL 155 (F)
THCL 155 (F)
Protection type
IP 54
IP 54
IP 54
Motor contactor
Thermal contact
Thermal contact
Thermal contact
Terminal strip heating without AL-KO rotation speed control
Fan 3x400 V 50 Hz
Fan 3x400 V 50 Hz
Fig.: Connection scheme for 1-level operation
Fig.: Connection scheme for 1-level operation
Figure:
Low rotation speed (star connection)
Fig.:
High rotation speed (delta connection)
Terminal strip cooling without AL-KO rotation speed control
Fan 3x400 V 50 Hz
Condensate pump
Filling level sensor
max. 230 V 3 A
Fig.: Connection scheme for 1-level operation
Figu
Low rotation speed (star connection)