19
3910831
Subject to changes in keeping with technical developments!
Safety information:
Warning!
Caution!
Ensure that the power supply is interrupted at the fuse box before connecting, removing or replacing the conden-
sate pump.
Do not use the pump to remove flammable or explosive liquids.
Do not operate the pump in an explosive atmosphere.
The pump may only be used for pumping liquids that do not attack the pump material.
Do not touch the pump with wet hands or while standing on a wet floor.
The pump is not suitable for outside areas. It may not be dipped into water or exposed to frost.
Ensure that the pump is not more than 7 m (max. suction height) above the drip tray exit and not more then 20 m
(max. transport height) below the highest point of the condensate drain.
Connect a flexible condensate drain pipe (internal Ø6 mm) to the pump outlet sleeve and duct it into an appropriate
drain. Ensure that the flexible condensate drainage line does not have sharp kinks, is not twisted and does not touch
any moving or sharp-edged objects.
We recommend testing the function of the pump in relation to the transport height before the initial operation of the
system. Fill the water into the collecting container of the device and check the function of the pump. Ensure that the
pump switches on after the starting point has been reached and switches off once pumping has been completed.
The air cooling system must switch and the media supply must be stopped once the alarm contact has been reached
or in the event of a fault.
1
2
3
4
5
1
Condensate pump
2
Suction pipe
3
Pressure pipe
4
Floating alarm contact
5
Connection cable 3-core
Fig.: Condensate pump
“Assembly”