Service Menu
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
17
– format the USB mass storage (16 GB max.) to FAT32
– create a folder named
APP
in the root directory
– open the project in CODESYS and select
Build -> Build
in the menu
– select
Online -> Create Boot Application
in the menu to create a boot application
for PLC
– select a folder on the PC drive in the pop-up dialog box
Save As ...
to save the boot
application
– copy the content of the selected folder in the folder
APP
on the USB mass storage
– connect the USB mass storage to the PLC
– power on the PLC and enter the Service Menu
– select
RESCAN USB DRIVE
– select
UPDATE PROJECT
The new project is transferred to the SPK and will be executed immediately.