35
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
6.5 Restore default settings
CAUTION
After restoring the factory settings, all previously configured settings, except network settings,
will be deleted.
To restore the factory settings and reset the installed password:
1. Switch on the power.
2. Press and hold the service button for more than 12 seconds.
3. Switch off and switch on the Device.
After turning on, the Device will work with default settings.
6.6 Real-time clock setting
The real-time clock (RTC) can be set or read from the Module via Modbus registers and also using
the akYtec Tool Pro program (see the program help).
To set a new time via Modbus registers:
1. Write the time value in the appropriate registers.
2. Set the value
1
in the current time update register for at least 1 second.
3. Write the value
0
in the current time update register.
The next writing of the current time can be made after 1 second.
6.7 Forcing counter reset
If the input state counter overflows, then the corresponding register is reset automatically. To force
the counter to zero, write the value 0 to the counter reset register.