18
akytec GmbH - Vahrenwalder Str. 269 A - 30179 Hannover - Germany Tel.: +49 (0) 511 16 59 672–0 - www.akytec.de
Fig. 4.7 Wye connection
NOTICE
1. Maximum length of communication lines: 100 m.
2. Connection is possible to any Ethernet port of the module.
3. The unused Ethernet port must be closed with a blanking plug.
To connect to the Daisy-chain scheme, you must use both Ethernet ports of Module. If Module fails
or the power is turned off, the data will be transferred from port 1 to port 2 without disconnecting.
Fig. 4.8 Daisy-chain connection
NOTICE
1. The maximum length of the communication line between two adjacent active devices
when connected with the “Daisy-Chain” must be not more than 100 m.
2. An adjacent connection scheme is allowed.
3. The unused Ethernet port should be closed with a blanking plug.