Plumbing
18
Water Requirements
COLD WATER FEED ONLY - Never fit the appliance to the hot water supply.
The shower hose retainer (supplied in the accessory pack) should be used. The installation should
comply with Water Regulations and prevent water supply contamination.
To ensure activation of the heating elements, the shower must be connected to a mains cold water
supply with a minimum running pressure of 50kPa (0.5 bar) recommended 1 bar with a maximum
static pressure of 1000kPa (10 bar).
Note
: For optimal product performance the recommended minimum dynamic water pressure should
be 100kPa (1 Bar). Dynamic pressure should not fall below 50kPa (0.5 bar) for example when other
draw off’s are used, such as a flushing the toilet as this may cause the shower temperature to
fluctuate dramatically.