Replacement Procedures for previous type PMS with new type
Please use the following steps if your replacing an old type PMS with this new type
PMSFL in the same Modbus string.
1. Check and take note the
new
PMSFL meter's LCD to see what is its current Modbus ID and
also the old type PMS that it will be replacing.
2. Connect the
new
PMSFL power meter to a SEC's RS485 bus which doesn't have the ID noted
in step #1 and the ID which the PMS will be changed to (old PMS ID).
3. Use the SEC UI to change the new PMSFLS's ID to the old PMS ID that it will replace.
4. Delete the old power meter from the securityProbe’s web UI (disable the meter and remove
the meter)
5. Physically replace the old power meter with the new PMSFL meter in the string.
6. Add the new power meter manually or Scan with add the meter automatically from the web
UI.
7. Turn online the sensor readings required. Only turn online 4 readings or less at a time before
saving.