Three Phase and Three Phase CT Type PMSFL User Manual - 13
PMS as ID 1.
2. Connect the second PMS, run the scan ID, set this PMS to ID 2, and then remove this
PMS both physically and from the web interface. This will hard code the PMS as ID 2.
3. Connect the third PMS, run the scan ID, set this PMS to ID 3, and then again remove
this PMS, both physically and from the web interface. This will hard code the PMS as ID
3.
4. Repeat this procedure with all PMS's you plan on connecting.
Note:
This will guarantee all of the PMS's in the daisy chain will function normally
without any problem and insure there are no duplicate PMS ID numbers in the chain.
5. After you have completed the pre-
configurations of all of your PMS’s that you are
going to connect, then reconnect each of them again in the same numerical sequence
as you previously configured them with. Start with PMS ID 1 and PMS ID 2. If these are
working OK, then you can connec
t the other PMS’s in the string.
Note
: Connect PMS ID 1 and PMS ID 2 on the same bus. Take caution that RS485 A
and RS485 B should not be swapped.
Basic Setup Of your PMS
Once you have connected your PMS unit to the securityProbe and you have ensured
correct power connection to the PMS, navigate to the web interface of your
securityProbe. You should be bought to summary page :-
After you have clicked the "Sensors" tab you will be bought to the sensor settings page:-