15
EN
•
Return temperature
1
.
(Not available on 3.5.0 or later version AZCE6THINKR)
(Only
available in installations with AZX6SONDPROTEC protection probe)
This allows you to
define the system's cut-off temperatures for the protection of the AC unit in heating mode
(32 °C, 34 °C and 36 °C) and cooling mode (6 °C, 8 °C and 10 °C). By default, the system's
heating cut-off temperature is set to 34 °C and the cooling cut-off temperature is set to 8 °C.
•
Radio channel.
This allows you to enable/disable the system's wireless association channel.
•
Reset system.
(Only available for Airzone Blueface zero master thermostats)
This allows
you to reset the system by returning it to factory settings. To reconfigure the thermostats,
go to the "Initial configuration" section.
•
Information.
(Only for Airzone Think thermostats)
This allows you to display information
about:
-
Zone:
firmware, zone, association, actuator or communications status.
-
System:
firmware, IAQ firmware, settings and information on system and installation
controllers.
-
Devices:
indicates the elements connected to the system.
-
Webserver:
firmware, IP address, gateway, MAC and PIN.
•
Q-Adapt
1
.
(Only for Airzone Think thermostats)
1.
In direct expansion units.
This allows you to define the airflow control algorithm that
best fits the duct installation. The options available are:
-
Maximum:
the system operates at maximum speed regardless of the number of zones.
-
Power
: the system operates at a higher speed than in Standard mode to ensure airflow
is increased.
-
Standard (by default):
the system changes speed depending on the number of zones.
-
Silence:
the system operates at a lower speed than in Standard mode to improve noise
reduction.
-
Minimum:
the system operates at minimum speed regardless of the number of zones.
2.
In fancoil units 0-10V.
This allows you to set the minimum (1.5 V by default) and
maximum (10 V by default) working voltage of the fan of the controlled AC unit, in 1 V
steps. The minimum voltage will correspond to the desired minimum speed of the AC
unit and the maximum voltage will correspond to the maximum speed. The average
speed will correspond to the midpoint between the two.
•
Relay settings
1
.
(Only for Airzone Cloud)
This allows you to change the operation logic of the
main control board's CMV/Boiler relay. By default, it is set to CMV.
•
Standby mode
1
.
(Only for Airzone Cloud)
Configuration of the operation logic of the
motorized elements when there is no demand on the system. This is disabled by default. If
enabled, from Airzone Cloud only the following can be configured:
- Standby mode for cooling: allows you to activate or deactivate Standby in cooling mode
- Standby mode for heating: allows you to activate or deactivate Standby in heating mode
- Heating Hysteresis: sets a hysteresis value in heating mode (by default 3 °C)
- Cooling Hysteresis: sets a hysteresis value in cooling mode (by default 1°C)
•
Filter maintenance
1
.
(Only for Airzone Cloud) It is used to enable or disable the warning,
edit hours of operation or reset the filter maintenance count
.
1
Parameters not available in Airzone Blueface zero thermostats