7
ICE CFA1120A-3360A & CGA3180A I&O Manual 03/2021 Rev.5
Model Number
CFA1120
CFA1150/3150
CFA3180
CFA3240
CFA3300
CFA3360
CGA3180
Cooling BTUH
1
125,000
150,000
182,200
216,600
300,000
330,000
180,000
Rated Air Flow (CFM
2
)
4,500
4,500
6,500
7,400
11,900
10,200
6,000
ESP
3
@ Rated Conditions
0.30
0.35
0.35
0.40
0.45
0.55
0.35
1
Cooling rated at 95°F (35°C) outdoor and 80°F DB/67° WB (26.5°C DB/19.5°C WB) return air
2
CFM=Cubic Feet per Minute
3
ESP=External Static Pressure
Ratings are with no outside air. Performance will be affected by altitude.
Ratings are at 230 volts for 208/230 volt units (“C” models), 460 volts for “D” models, 380 volts for “E” models, 575 volts for “Z” models. Derate
performance by 17% for ACE (380v. 3ø, 50 Hz) models
Operation of units at a different voltage from that of the rating point will affect performance and air flow.
Table 1. Cooling Performance and Air Flow Ratings
MODEL
Description
INCHES MILLIMETERS PART #
# OF
FILTERS
MERV
RATING
CFA1120/1150 & CFA3150
For Optional Fresh Air Hood
11 x 22 x 1 279 x 559 x 25 80119
2
N/A
CFA1120/1150 & CFA3150
Exterior Access Return Air Filter
25 x 16 x 2 635 x 406 x 51 80137
3
8
CFA1120/1150 & CFA3150
Interior Access Return Air Filter
15 x 20 x 2 381 x 508 x 51 92365
3
8
CFA1120/1150 & CFA3150 w/Economizer
Fresh Air Hood Pre-filters
26 x 12 x 1” 660 x 305 x 25 92526
2
N/A
CFA1120/1150 & CFA3150 Reverse Flow w/Economizer
Economizer Pre-filter
9
1
/
4
x 37 x
3
/
8
235 x 940 x 10 92127
1
N/A
CFA3180/3240
Exterior Access Return Air Filter
25 x 16 x 2 635 x 406 x 51 80137
4
8
CFA3180/3240
Interior Access Return Air Filter
24 x 18 x 2 610 x 457 x 51 81257
4
8
CFA3180/3240 w/Economizer
Fresh Air Hood Pre-filters
26 x 12 x 1 660 x 305 x 25 92526
2
N/A
CFA3180/3240 Reverse Flow w/Economizer
Fresh Air Hood Pre-filters
16 x 32 x 1 406 x 813 x 25 93187
3
N/A
CFA3300/3360
Exterior Access Return Air Filter
30 x 30 x 2 762 x 762 x 51 80156
4
8
CFA3300/3360
Interior Access Return Air Filter
24 x 18 x 2 610 x 457 x 51 81257
4
8
CGA3180
Exterior Access Return Air Filter
30 x 30 x 2 762 x 762 x 51 80156
4
8
CGA3180
Interior Access Return Air Filter
24 x 18 x 2 610 x 457 x 51 81257
4
8
CGA3180
For Optional Fresh Air Hood, #K/04657 26 x 12 x 1 660 x 305 x 25 92526
2
N/A
CGA3180 Reverse Flow
Exterior Access Return Air Filter
30 x 30 x 2 762 x 762 x 51 80156
4
8
CGA3180 Reverse Flow
Interior Access Return Air Filter
24 x 18 x 2 610 x 457 x 51 81257
4
8
Table 2. Filter Sizes/Part Numbers
MODEL
Unit Weight
Shipping Weight
Shipping Dimensions
Height
Width
Depth
LBS
KG
LBS
KG
Inches
MM
Inches
MM
Inches
MM
CFA1120
1,160
527.3
1,285
584.1
98
2,489
56
1,422
48
1,219
CFA1150 & CFA3150
1,166
530
1,291
586.8
98
2,489
56
1,422
48
1,219
CFA3180
2,307
1,046
2,420
1,098
98
2,489
76
1,930
51
1,295
CFA3240
2,523
1,144
2,636
1,196
98
2,489
76
1,930
51
1,295
CFA3300
2,625
1,193
2,750
1,250
108
2,743
72
1,829
72
1,829
CFA3360
3,210
1,456
3,335
1,513
108
2,743
72
1,829
72
1,829
CGA3180
3,210
1,456
3,335
1,513
108
2,743
72
1,829
72
1,829
Table 3. Shipping Weights & Dimensions
Model
CFA1120
CFA1150 CFA3150 CFA3180 CFA3240 CFA3300 CFA3360 CGA3180
Refrigerant Charge (Oz)
367
367
152
1
240
1
264.5
1
432
1
416
1
320
1
1
Per circuit on dual compressor models
Table 4. Refrigerant Charge (R410A, Ounces)
1.5 General Operation
Hot Gas By-Pass
Normally used in specialty applications (i.e Magnetic Resonance Imaging (MRI) buildings) to prevent
magnetic voltage disturbance caused by cycling. This technology is applied in this product to extend
the operation envelope for the compressor to 20º F (-6.6ºC). Combined with a condenser low ambient
Fan Cycle feature, compressor operation can be extended to 0º F (-17.8ºC). During Hot Gas operation
mode, system performance will be reduced. If product operation is in mild outdoor ambient conditions,
the installed shut-off ball valve may be closed, thus disabling the Hot Gas By-Pass feature.
Refrigerant Cycle (Cooling Mode)
The air conditioners use R-410A refrigerant in a conventional vapor-compression refrigeration cycle to
transfer heat from air in an enclosed space to the outside. A motorized impeller assembly blows indoor
air across the evaporator. Cold liquid refrigerant passing through the evaporator is boiled into gas by
heat removed from the air. The warmed refrigerant gas enters the compressor where its temperature and